14
2 SPECIFICATIONS
2.1 General Specifications
2
SPECIFICATIONS
This chapter describes the specifications of FX5-8AD.
2.1
General Specifications
The general specifications other than below are the same as those for the CPU module to be connected.
For general specifications, refer to the following.
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
2.2
Power Supply Specifications
The following table lists the power supply specifications.
2.3
Performance Specifications
The following table lists the performance specifications.
*1 In the case of 2CH conversion mode, conversion speed is 1 ms/2ch.
*2 FX5-CNV-IFC or FX5-C1PS-5V is necessary to connect FX5-8AD to the FX5UC CPU module.
Items
Specifications
Dielectric withstand voltage
500 V AC for 1 minute
Between all terminals and ground terminal
Insulation resistance
10 M
Ω
or higher by 500 V DC
insulation resistance tester
Items
Specifications
External power supply
Power supply voltage
24 V DC +20%, -15%
Allowable momentary
power outage time
Operation continues when the instantaneous power failure is shorter than 5 ms.
Current consumption
100 mA
Internal power supply
Power supply voltage
24 V DC
Current consumption
40 mA
Items
Specifications
Number of input points
8 points (8 channels)
Conversion speed
Voltage/Current
1 ms/ch
Thermocouple/
Resistance temperature
detector
40 ms/ch
Isolation method
Between input terminal
and PLC
Photocoupler
Between input terminal
and channels
Non-isolation
Number of occupied I/O points
8 points
Applicable CPU module
FX5U CPU module (Ver.1.050 or later)
FX5UC CPU module
(Ver.1.050 or later)
Applicable engineering tool