8 - 40
8. BUS CONNECTION
8.4 Precautions
8.4.12
When connecting multiple
GOTs
(1) System including different GOT series
The GOT2000 series can be connected with GOT1000
series and GOT-A900 series in a system.
When using them together, refer to the following
Technical News.
Precautions when Replacing GOT1000 Series
with GOT2000 Series (GOT-A-0061)
Precautions when Replacing GOT-A900 Series
with GOT2000 Series (GOT-A-0062)
The GOT2000 series cannot be used with GOTs other
than GOT1000 or GOT-A900 series in a system.
(2) Restrictions on No. of GOTs
The number of connectable GOTs is restricted
according to the CPU type and the number of intelligent
function modules.
*1
Indicates the following models:
AD51(S3), AD51H(S3), AD51FD(S3), AD57G(S3),
AJ71C21(S1), AJ71C22(S1), AJ71C23, AJ71C24(S3/S6/
S8), AJ71UC24, AJ71E71(-S3), AJ71E71N-B2/B5/T/B5T,
AJ71E71N3-T, AJ61BT11 (in intelligent mode only),
A1SJ71C24(-R2/PRF/R4),
A1SJ71UC24(-R2/PRF/R4),
A1SJ71E71-B2/B5(-S3),
A1SJ71E71N-B2/B5/T/B5T, A1SJ71E71N3-T, A1SD51S,
A1SJ61BT11 (in intelligent mode only)
*2
Only the A1SD51S can be connected to the QCPU (Q
Mode).
8.4.13
When using a PLC CPU in the
direct mode
Note that when the I/O control mode of the PLC CPU is the
direct mode, and if the 1st GOT is connected to the main or
extension base unit with a 5m extension cable (GT15-
AC50B, GT15-A1SC50NB), the input X of the empty I/O
slot cannot be used.
No restrictions apply when the I/O control mode is the
refresh mode.
On PLC CPUs whose I/O control mode can be selected by
a switch, set the I/O control mode to the refresh mode
before use.
POINT
POINT
POINT
In the cases where input X of an empty I/O slot is used
(1) When input X is assigned on the MELSECNET/10
network
(2) When input X of an empty I/O slot is turned ON/
OFF by the computer link module
(3) When input X of the I/O slot is turned ON/OFF by
the touch switch function (Bit SET/RST/Alternate/
Momentary) of GOT
When connecting to
Number of
connectable
GOTs
Total number of
connectable GOTs
and intelligent
function modules
*1
QCPU(Q mode),
motion controller CPU (Q Series)
Up to 5
5 GOTs
+ 6 intelligent
function modules
*2
QCPU (A mode)
Not
connectable
―――――
QnACPU
Up to 3
6 in total
ACPU
AnUCPU,
AnACPU,
A2US(H)CPU
Up to 3
6 in total
AnNCPU,
AnS(H)CPU,
A1SJ(H)CPU
Up to 2
2 in total
A0J2HCPU
Up to 1
2 in total
A1FXCPU
Not
connectable
―――――
Motion
controller
CPU
(A Series)
A273UCPU,
A273UHCPU(-S3),
A373UCPU(-S3),
A173UHCPU(-S1)
Up to 3
6 in total
A171SHCPUN,
A172SHCPUN
Up to 2
2 in total
GOT-A900
GOT1000
GOT800
Summary of Contents for GOT2000 Series
Page 2: ......
Page 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 64: ......
Page 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Page 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Page 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Page 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Page 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Page 416: ......
Page 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Page 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Page 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Page 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Page 542: ......
Page 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Page 568: ......
Page 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Page 600: ......
Page 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Page 670: ...REVISIONS 2 ...
Page 673: ......