15.3 FX List Editor (For GT104[ ], GT105[ ] only)
15.3.7 Selection and operation of modes
15.3.7 Selection and operation of modes
The MELSEC-FX list editor has four modes: READ, WRITE, INSERT, and DELETE.
Select an appropriate mode for the intended operation.
For more information on the mode to select, refer to the function operations from subsection 15.3.8 onward.
1
How to change modes
Touch the
button.
Each time you touch this button, the mode changes.
2
In the case the mode cannot be changed
In the following cases, only READ mode is allowed.
If you try to change to other than READ mode, an error message is displayed.
To change to other than READ mode, take the action below.
Error Message
Description
Corrective action
PLC is running
The FX PLC is in the RUN status.
Stop the FX PLC.
Can not write.
The protect switch of the EEPROM memory
cassette is on.
Switch off the protect switch of the EEPROM
memory cassette.
The EPROM memory cassette is enabled.
Set a memory other than EPROM as the memory
to write to.
MODE
Touch the button.