This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310,
JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
3.1 Applicable cable and terminal tightening torque
3.1.1
Terminal block (European type)
1) Wire size
- The power supply wire should use 22-20 AWG wire.
2) Applicable cable
3) Termination of cable end
Strip the coating of strand wire and twist the cable core before connecting it, or
strip the coating of single wire before connecting it.
An alternative connection is to use a ferrule with insulating sleeve.
*1 Old model name: CRIMPFOX ZA 3
*2 Old model name: CRIMPFOX UD 6
When using a stick terminal with insulating sleeve, choose a wire with proper
cable sheath referring to the above outside dimensions, or otherwise, the wire
cannot be inserted easily.
The tightening torque must be 0.22 to 0.25N
•
m. Do not tighten terminal screws
exceeding the specified torque. Failure to do so may cause equipment failures
or malfunctions.
3.2 Power Supply Wiring
For the power supply wiring, refer to the following manual.
→
FX
3G
/FX
3U
/FX
3UC
Series User's Manual - Analog Control Edition
WIRING
PRECAUTIONS
•
Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the
PLC. However, do not use common grounding with heavy electrical
systems.
•
Make sure to properly wire to the terminal board (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual.
- Tighten to torque should follow the torque described in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
•
Make sure to properly wire to the FX
3G/
FX
3U
/FX
3UC
Series PLC in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual of the PLC main unit.
- Tightening torque should follow the specifications in the manual of the
PLC main unit.
Type
Wire size
Single-wire
0.3mm
2
to 0.5mm
2
(AWG22 to 20)
2-wire
2 pieces of 0.3mm
2
(AWG22)
Manufacturer
Model
Pressure bonding tool
Phoenix Contact Co., Ltd.
AI 0.5-8WH
CRIMPFOX 6
*1
(or CRIMPFOX 6T-F
*2
)
9mm
(0.35")
- Strand wire/single wire
8mm
(0.31")
Contact area
(Crimp area)
14mm(0.55")
2.6mm(0.1")
Insulation sleeve
- Stick terminal with insulating sleeve
3.3 Selection of resistance thermometer sensors
→
For the terminal layout, refer to Section 1.2
Precautions on resistance thermometer wiring
•
When using a 2-wire temperature sensor type, short-circuit the [L-] terminal and the
[I-] terminal. For the lead wire use a 10
Ω
resistance or less per line.
•
Separate the cable of the resistance thermometer sensors from the other power
cables or areas easily affected by inductive noise (of the commercial power, etc.).
Example of resistance thermometer wiring
*1 24V DC service power supply of the FX
3G
/FX
3U
Series PLC can also be used.
*2 When using a 2-wire temperature sensor type, short-circuit the [L
-] terminal
and the [I
-] terminal.
3.4 Grounding
Grounding should be performed as stated below.
•
The grounding resistance should be 100
Ω
or less.
•
Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of the
following figure.
For details, refer to the following manual.
→
FX
3G
Series User's Manual - Hardware Edition
→
FX
3U
Series User's Manual - Hardware Edition
→
FX
3UC
Series User's Manual - Hardware Edition
•
The grounding wire size should be AWG 22-20 (0.3-0.5 mm
2
).
•
The grounding point should be close to the PLC, and all grounding wire should be
as short as possible.
4. Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
•
Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric distributor.
•
Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
•
Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
1M
Ω
ch
PNK-ADP
Class-D grounding
+5V
24+
24-
Shield wire
Terminal
block
24V DC
*1
L
+, L
-, I
-, ch
:
represents the channel number.
3-wire
sensors
type
1M
Ω
47k
Ω
47k
Ω
+5V
1M
Ω
ch
+5V
1M
Ω
47k
Ω
47k
Ω
2-wire
sensors
type
L
-
I
-
L
+
L
-
I
-
L
+
*2
Resistance thermometer
wiring
External power supply
wiring
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
4.1 Applicable PLC
The version number can be checked by monitoring D8001 as the last three digits
indicate it.
4.2 General Specifications
For the general specifications, refer to the manual of the PLC main unit.
The items other than the following are equivalent to those of the PLC main unit.
→
FX
3G
Series User's Manual - Hardware Edition
→
FX
3U
Series User's Manual - Hardware Edition
→
FX
3UC
Series User's Manual - Hardware Edition
4.3 Power Supply Specifications
4.4 Performance Specifications
TRANSPORT AND
STORAGE PRECAUTIONS
•
The product is a precision instrument. During transportation, avoid any impacts.
Failure to do so may cause failures in the product. After transportation, verify the
operations of the product.
Model name
Applicability
FX
3U
Series PLC
Ver. 2.20 or later (from first production)
FX
3UC
Series PLC
Ver. 1.30 or later (from the production manufactured in
August, 2004 with SER No. 48****)
FX
3G
Series PLC
Ver. 1.00 or later (from first production)
Item
Specification
Dielectric withstand
voltage
500V AC for one minute
Between all terminals and
ground terminal of PLC
main unit
Insulation resistance
5M
Ω
or more by 500V DC
megger
Item
Specification
A/D conversion
circuit driving power
24V DC +20%/-15%, 50mA for 24V DC
Connect a 24V DC power supply to the terminal block.
Interface driving
power
5V DC, 15mA
5V DC power is supplied from the internal power supply
of main unit.
Item
Description
Centigrade (
°
C)
Fahrenheit (
°
F)
Input signal
Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
JIS C 1604-1997
Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
DIN 43760-1987
Rated
temperature
range
Pt1000
-50
°
C to +250
°
C
Pt1000
-58
°
F to +482
°
F
Ni1000
-40
°
C to +110
°
C
Ni1000
-40
°
F to +230
°
F
Digital output
Pt1000
-500 to +2500
Pt1000
-580 to +4820
Ni1000
-400 to +1100
Ni1000
-400 to +2300
Resolution
Pt1000
0.1
°
C
Pt1000
0.2
°
F
Ni1000
Ni1000
Total
accuracy
±
0.5% for full scale (when ambient temperature is 25
°
C
±
5
°
C)
±
1.0% for full scale (when ambient temperature is in the range of 0
to 55
°
C)
A/D
conversion
time
•
FX
3U
/FX
3UC
Series PLC : 200
µ
s
(The data will be updated at every scan time of the PLC.)
•
FX
3G
Series PLC : 250
µ
s
(The data will be updated at every scan time of the PLC.)
Item
Description
Centigrade (
°
C)
Fahrenheit (
°
F)
Input charac-
teristics
Insulation
method
•
The photocoupler is adopted to insulate the analog input area
from the PLC.
•
The DC/DC converter is adopted to insulate the power supply
line from the analog input area.
•
Channels are not insulated from each other.
Occupied
points
0 point (This number is not related to the maximum number of
input/output points of the PLC.)
0
+250
°
C
+2500
-50
°
C
-500
A
pprox
.
-5
5
°
C
A
pprox
.
+
256
°
C
- Pt1000
+2560
-550
0
+110
°
C
+1100
-40
°
C
-400
Ap
pr
ox
.
+1
15
°
C
- Ni1000
+1150
-450
A
pprox
.
-4
5
°
C
0
+482
°
F
+4820
-58
°
F
-580
A
ppr
ox
.
-67
°
F
Ap
pr
ox
.
+4
92
.8
°
F
- Pt1000
+4928
-670
0
+230
°
F
+2300
-40
°
F
-400
Ap
pr
ox
.
+2
39
°
F
- Ni1000
+2390
-490
A
pprox
.
-4
9
°
F