FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
57
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.3 Input Specifications
1
Introducti
on
2
Features
and
Par
t Names
3
Product
Introduc
tion
4
Sp
eci
fic
ati
ons
5
V
ers
ion and
Peri
ph
er
al
D
evices
6
S
yst
em
C
onfi
guration
7
Input/Ou
tput
No
s., Un
it No
s.
8
Inst
allati
on
9
Prep
arati
on an
d
Pow
er Supp
ly
Wi
rin
g
10
Input W
iring
4.3.2
100V AC input type
→
For handling of 100V AC input, refer to Subsection 10.3.2.
Item
Specifications
FX
3U
-32MR/UA1
FX
3U
-64MR/UA1
Input points
16 points
32 points
Connection type
Removable terminal block (M3 screw)
Input form
AC input
Input signal voltage
100 to 120V AC
+
10%, -15% 50/60Hz
Input impedance
Approx. 21k
Ω
/50Hz
Approx. 18k
Ω
/60Hz
Input signal current
4.7 mA/100V AC 50 Hz (70% or less when turned on simultaneously)
6.2 mA/110V AC 60 Hz (70% or less when turned on simultaneously)
ON input sensitivity current
3.8 mA or more
OFF input sensitivity current
1.7 mA or less
Input response time
Approx. 25 to 30 ms (A high-speed receiving is improper)
Input signal form
Contact input
Input circuit insulation
Photo-coupler insulation
Indication of input operation
LED on panel lights when input.
Input circuit diagram
*1 Input impedance
N
L
100 to 240V AC
100 to 120V AC
Fuse
X
COM
*1