![Mitsubishi FR - S500 Instruction Manual Download Page 64](http://html1.mh-extra.com/html/mitsubishi/fr-s500/fr-s500_instruction-manual_1809246064.webp)
54
Function (Parameter) list
P
ara
me
te
r L
ist
O
per
at
io
n s
el
ect
io
n
fu
n
ctio
ns
70
Soft-PWM
setting
Presence/absence of
Soft-PWM control can
be selected.
When Soft-PWM is
valid, the metallic tone
of motor noise can be
changed into
unoffending composite
tone.
0: Soft-PWM invalid
1: Soft-PWM valid
1
1
103
71
Applied motor
0, 100:
Thermal characteristic
for Mitsubishi
standard motor
1, 101:
Thermal characteristic
for Mitsubishi
constant-torque motor
(Thermal characteristic
for Mitsubishi constant-
torque motor is
selected with the RT
signal ON when 100
and 101 are set.)
1
0
69
72
PWM
frequency
selection
0 to 15
1
1
103
73
0-5V/0-10V
selection
0: For 0 to 5VDC input
1: For 0 to 10VDC input
1
0
104
74
Input filter
time constant
0: 2-step moving
average processing
1 to 8:
Exponential
average value of 2n
at the setting of n
1
1
105
Func-
tion
Para-
meter
Indica-
tion
Name
Setting Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Cus-
tomer
Setting
Summary of Contents for FR - S500
Page 56: ...46 MEMO ...
Page 164: ...154 MEMO ...
Page 188: ...178 MEMO ...
Page 189: ...179 APPENDIX APPENDIX 1 Parameter Instruction Code List 180 ...