6
Specifications
5
Specifications
*1
The power factor is calculated on the assumption that the power impedance is 1%. The
value changes according to the power supply capacity and power impedance. The load is
calculated using the fundamental current specified in JEM-TR201 as 100%.
The value is 94.4% when calculated with 1 power factor for the fundamental wave
according to the Architectural Standard Specifications (Electrical Installation) (2013
revision) supervised by the Ministry of Land, Infrastructure, Transport and Tourism of
Japan.
For a motor of less than 0.4kW, the power factor improving effect will be slightly lower.
Power factor improving effect *1
Power supply power factor approx. 93%(94.4%)
(at 100% load)
Power specifications
200V class Three-phase 200 to 240VAC 50Hz/60Hz
400V class
55K or
lower
Three-phase 380 to 480VAC
50Hz/60Hz
75K or
higher
Three-phase 380 to 500VAC
50Hz/60Hz
E
n
viron
m
en
t
Surrounding air
temperature
-10°C to + 50°C (non-freezing)
Ambient humidity
90%RH or less (non-condensing)
Storage temperature
-20°C to + 65°C (non-freezing)
Atmosphere
Indoors (free from corrosive gas, flammable gas, oil
mist, dust and dirt)
Altitude/vibration
Max.1000m above sea level 5.9m/s
2
or less