143
-
2.2.6
Piping system
Flare connceting
Cooling cycle
Heating cycle
Thermistor
(Th
I
-R2)
Thermistor
(Th
I
-R1)
Thermistor
(Th
O
-D)
Thermistor
(Th
O
-S)
Thermistor
(Th
O
-A)
Service valve
(Flare connecting)
Service valve
(Flare connecting)
High pressure
switch
Low pressure
sensor
(63H1)
(LPT)
Thermistor
(Th
O
-R)
(SV1)
(EEVH)
Thermistor
(Th
I
-A)
Heat exchanger
Heat
exchanger
Solenoid
valve
Strainer
Strainer
Strainer
Strainer
Liquid line
(ø9.52)
Liquid branch
pipe
(ø9.52)
(ø6.35)
(ø6.35)
Gas line
Branch pipe
(Barzing)
Branch pipe
(Barzing)
(ø15.88)
Gas branch pipe
(ø15.88)
4way valve
Muffler
Muffler
Compressor
Compressor
accumlator
Check joint
Check joint
Check valve
Indoor unit
Outdoor unit
Electronic
expansion valve
Electronic
expansion valve
(EEVC)
Strainer
Strainer
Receiver
Preset point of the protective devices
Parts name
Mark
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Thermistor
(for detecting dis-
charge pipe temp.)
High pressure switch
(for protection)
OFF 63C
ON 56C
Equipped
unit
Th
I-
R
Tho-D
63H1
Indoor unit
Outdoor unit
Outdoor unit
OFF 1.0C
ON 10C
FDCVA302HENR
OFF 4.15MPa
ON 3.15MPa
Low pressure sensor
(for protection)
LPT
Outdoor unit
OFF 0.227MPa
ON 0.079MPa
OFF 115C
ON 85C
Indoor unit
Notes (1) If used in combination with 151 series indoor units, make the fluid pipe size on the branch piping (branch to indoor unit) ø9.52.
(2) A FDEN type strainer only should be used for the indoor unit.