F930GOT-BBD-K-E

Installation Manual

JY997D02501B

This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the F930GOT-BBD-K-E and should be read and understood before
attempting to install or use the unit. Further information can be found in the associated manuals list below.

Specifications are subject to change without notice

Guidelines for the Safety of the User and Protection of the 
F930GOT-BBD-K-E

This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:

a) Any engineer using the product associated with this manual, should be of a competent nature,

trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.

b) Any commissioning or service engineer must be of a competent nature, trained and qualified to

the local and national standards.

c)

All operators of the completed equipment should be trained to use that product in a safe and 
co-ordinated manner in compliance to established safety practices.

Note:

The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.

Note’s on the Symbols Used in this Manual

At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.

1) Indicates that the identified danger 

WILL

 cause physical and property damage.

2) Indicates that the identified danger could 

POSSIBLY

 cause physical and property

damage.

Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.

All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the
product based on these illustrative examples.

Owing to the very great variety in possible application of this equipment, you must satisfy yourself as
to its suitability for your specific application.

Associated Manuals

!

Indispensable manual

"

Either manual is necessary.

Refer to the manual of the connected programmable controller for details concerning that unit. 

Manual Name

Manual Number

Description

!

GOT-F900 Series 
Operation Manual 

JY992D94701

This manual contains explanations for the 
operation and use of the GOT-F900 series 
graphic operation terminals.

!

GOT-F900 Series 
Hardware Manual 
(connection diagram)

JY992D94801

This manual contains explanations for the 
wiring and installation, etc. of the GOT-F900 
series graphic operation terminals.

"

FX-PCS-DU/WIN-E 
SOFTWARE MANUAL

JY992D68301

This manual contains explanations for the 
operation of FX-PCS-DU/WIN-E screen design 
software.

"

SW*D5C-GOTR-PACKE
Operating Manual

-

This manual contains explanations for the 
operation of GT-Designer (SW*D5C-GOTR-
PACKE) screen design software.

1. Introduction

The F930GOT-BBD-K-E (hereafter called “GOT”) is to be mounted
on the face of a control panel or operations panel, and connected
to the programming port (CPU port) or the communication port
(communication units port) of a PLC.
Various devices can be monitored and PLC data changed through
the screens in the GOT. Several display screens are built-in to the
GOT, and additional personalized screens can be created by the
user.

1) The GOT can connect to MELSEC FX, A, QnA and Q PLCs

as well as a host of third party manufactured units. Further
information can be found in GOT-F900 Series Hardware
Manual.

2) Through the GOT, PLC user programs can be downloaded, uploaded and monitored in programming

software GX-Developer or FX-PCS/WIN-E on a personal computer. Further information can be found
in GOT-F900 Series Operation Manual.

3) Display screens are created using the following software. 

1.1 Product Lists

Caution

During abnormal communication (including cable breakage) when monitoring within the GOT,
communication between the GOT and programmable controller CPU is interrupted and it is
impossible to operate switches or devices in the PLC via the GOT. 
Communication and operation resumes when the GOT system is correctly configured.
DO NOT configure emergency stop or safety features to operate through the GOT, and be
sure that there is no adverse consequences in the event of a GOT - PLC communications
malfunction. 

Note;

Do not lay signal cables near high voltage power cables or allow them to share the same
trunking duct.
Otherwise effects of noise or surge induction are likely to occur. Keep a safe distance of
more than 100 mm from these wires.

Operate touch switches on the display screen by hand. 
DO NOT use excessive force, or attempt to operate them with hard or pointed objects.
The tip of a screw driver, pen or similar object for example may break the screen. 

Software Name

Version

GT Designer

Screen design software for Windows
SW5D5C-GOTR-PACKE Version 5.26C or more

FX-PCS-DU/WIN-E

Screen design software for Windows
SW0PC-FXDU/WIN-E Version V2.70 or more

Production Name

Description

F930GOT-BBD-K-E

Graphic operation terminal main unit.

FX-50DU-CAB0

Communication cable (GOT 

 CPU port in FX

0S

, FX

1S

, FX

0N

, FX

1N

, FX

2N

 or 

FX

2NC

 series PLC)

The connector on the GOT side is straight through.
Cable length is 3m (9' 10").

FX-50DU-CAB0/EN

Communication cable (GOT 

 CPU port in FX

0S

, FX

1S

, FX

0N

, FX

1N

, FX

2N

 or 

FX

2NC

 series PLC) 

The connector on the GOT side is straight through.
Cable length is 3m (9' 10").
Use FX-50DU-CAB0/EN for compliance to EC EMC.

FX-50DU-CAB0-**M

Communication cable (GOT 

 CPU port in FX

0S

, FX

1S

, FX

0N

, FX

1N

, FX

2N

 or 

FX

2NC

 series PLC)

The connector on the GOT side is straight through.
** M is cable length. 1M: 1m (3' 3"), 10M: 10m (32' 9"), 20M: 20m (65' 7"), 

30M: 30m (98' 5")

FX-40DU-CAB

Communication cable (GOT 

 CPU port in A or QnA series PLC)

The connector on the GOT side is straight through.
Cable length is 3m (9' 10").

FX-40DU-CAB-**M

Communication cable (GOT 

 CPU port in A or QnA series PLC)

The connector on the GOT side is straight through.
** M is cable length. 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5")

QC30R2

Communication cable (GOT 

 CPU port in Q series PLC)

The connector on the GOT side is straight through.
Cable length is 3m (9' 10").

FX-232CAB-1

Data exchange cable (GOT 

 Personal computer <9-pin D-sub>)

FX

2NC

-32BL

Battery for keeping Alarm history and current time data

F9GT-30PSC

Transparent protection sheet for F930GOT (5 pieces)

PLC

Programming

port

GOT

1.2 Dimensions and Each Part Name

Dimensions: mm (inches)

Mass (Weight):

0.6 kg (1.32 lbs)

Accessory:

Mounting brackets, Tightening bolt (M3, 4 bolts), 
Packing seal for dust and water resistance

a) Display

b) LED (green)
c)

Function keys

d) Cursor keys

e) 0 to 9 keys
f)

Mounting bracket and tightening
bolt (accessory)

g) Communication ports

h) FX

2NC

-32BL battery

i)

Communication cable (optional)

j)

DC power supply terminal (M3)

k)

Label insert

l)

Packing seal (accessory)

2. Specifications

2.1 General Specifications

2.2 Power Supply Specifications

Port

Description

COM0
(RS- 422)

RS-422 port for 
connecting PLC 
(including1:N 
connection) or 
communication 
(computer link) unit 
<9-pin D-sub>

COM1
(RS- 232C)

RS-232C port for 
connecting 
personal computer, 
printer, bar-code 
reader or 1:N 
connection
<9-pin D-sub>

Item

Specifications

Operating Temperature

0 ~ 50 °C (32 ~ 122 °F) 

Storage Temperature

-20 ~ 60 °C (-4 ~ 140 °F)

Humidity

35 ~ 85% Relative Humidity, No condensation

Vibration Resistance
 - intermittent vibration

Conforms to IEC 61131-2; 10 ~ 57 Hz: 0.075 mm Half Amplitude

                                       57 ~ 150 Hz: 9.8 m/s

2

 Acceleration

                  Sweep Count for X, Y, Z: 10 times (80 min. in each direction)

Vibration Resistance
 - Continuous vibration

Conforms to IEC 61131-2; 10 ~ 57 Hz: 0.035 mm Half Amplitude

                                       57 ~ 150 Hz: 4.9 m/s

2

 Acceleration

                  Sweep Count for X, Y, Z: 10 times (80 min in each direction)

Shock Resistance

Conforms to IEC 61131-2: 147m/s

2

 Acceleration, 

                                   3 times in each direction X, Y, and Z

Noise Immunity

1000 Vp-p, 1micro second, 30 ~ 100 Hz, tested by noise simulator

Dielectric Withstand Voltage

500 V AC > 1 min, tested between power terminals and ground

Insulation Resistance

5 M

 > at 500 V DC, tested between power terminals and ground

Ground

Grounding registance 100 

 or less.

Protection

IP65f level

Items

Specifications

Power Supply Voltage

24V DC, +10% -15%

Power Supply Ripple

200 mV or less

Current Consumption

Ratings: 220 mA at 24V DC
(120 mA at 24 V DC when backlight is turned OFF)

Fuse

Fuse built-in GOT (impossible to change)

Max. Allowable Momentary 
Power Supply Failure period

5 ms; If less than 5 ms, the GOT will continue operation. If 5 ms or 
more, the GOT will shut down.

Battery

Built-in, FX

2NC

-32BL type lithium battery. (Approximately 3 years life)

Guaranteed term is 1 year. 

154(6.06")

169(6.65")

COM1

RS232C

COM0

RS422

f)

g)

h)

l)

k)

i)

j)

Rear panel

168(6.61")

37.5(1.48")

6.4(0.25")

183(7.20")

Front panel

a)

c)

e)

d)

b)

Summary of Contents for F930GOT-BBD-K-E

Page 1: ...system is correctly configured DO NOT configure emergency stop or safety features to operate through the GOT and be sure that there is no adverse consequences in the event of a GOT PLC communications...

Page 2: ...system is correctly configured DO NOT configure emergency stop or safety features to operate through the GOT and be sure that there is no adverse consequences in the event of a GOT PLC communications...

Page 3: ...system is correctly configured DO NOT configure emergency stop or safety features to operate through the GOT and be sure that there is no adverse consequences in the event of a GOT PLC communications...

Page 4: ...perform common grounding of the GOT and a strong power system Note Feed power to the GOT by an external power supply The service power supply of the programmable controller cannot be used Confirm ser...

Page 5: ...perform common grounding of the GOT and a strong power system Note Feed power to the GOT by an external power supply The service power supply of the programmable controller cannot be used Confirm ser...

Page 6: ...perform common grounding of the GOT and a strong power system Note Feed power to the GOT by an external power supply The service power supply of the programmable controller cannot be used Confirm ser...

Page 7: ...system is correctly configured DO NOT configure emergency stop or safety features to operate through the GOT and be sure that there is no adverse consequences in the event of a GOT PLC communications...

Page 8: ...perform common grounding of the GOT and a strong power system Note Feed power to the GOT by an external power supply The service power supply of the programmable controller cannot be used Confirm ser...

Reviews: