OC292-35
PKFY-20NFMU-A
PKFY-32NFMU-A
Parts name
Check points
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 50
°
F~86
°
F)
Disconnect the connector then measure the resistance valve using a tester.
(Surrounding temperature 68
°
F)
Linear expansion
valve
(Refer to page OC292-36 for details.)
Room temperature
thermistor (TH21)
Liquid pipe temperature
thermistor (TH22)
Gas pipe temperature
thermistor (TH23)
Normal
4.3k
"
~9.6k
"
Abnormal
Open or short
Abnormal
Open or short
Normal
150
"
i
10%
1
-
5
White-Red
2
-
6
Yellow-Brown
3
-
5
Orange-Red
4
-
6
Blue-Brown
Orange
Red
White
Blue
Brown
Yellow
3
6
1
5
4
2
M
Measure the resistance between the terminals using a tester.
(Surrounding temperature 68
°
F)
Fan motor
1
3
3
2
5
1
Red
White
Black
FAN
Protector
PKFY-20NFMU-A
99.5
"
i
10%
103.5
"
i
10%
PKFY-32NFMU-A
62.6
"
i
10%
74.0
"
i
10%
Abnormal
Open or short
Red-Black
White-Black
Motor terminal or
Relay connector
Normal
Measure the resistance between the terminals using a tester.
(Surrounding temperature 68
°
F~86
°
F)
Vane motor
Normal
Connector
Abnormal
186~214
"
Open or short
Brown — Yellow
Brown — Blue
Red — Orange
Red — Pink
(Refer to page
OC292-36 for details.)
Blue
Yellow Brown
Orange
Red
Pink
2
3
4
5
6 1
M
OPEN : 266
I
9
°
F
CLOSE : 181
I
27
°
F
OC292--2.qxp 02.9.26 4:52 PM Page 35