Mitsubishi Heavy Industries 25ZMX-S Technical Manual Download Page 50

-

  

-

 '13 • SRK-T-144D

Press         or         button.

Make sure which do you want to set, "     FUNCTION     " 
(remote control function) or "I/U FUNCTION     " (indoor unit 
function).

Note 1: The initial setting marked “ ” is decided by connected indoor and outdoor unit, and is automatically defined as following table.

Function No.
Remote controller 

function02
Remote controller 

function06
Remote controller 

function07
Remote controller 

function13

Remote controller 

function15

Default

Model

Indoor unit with only one of air flow setting
Heat pump unit

Exclusive cooling unit

"Auto-RUN" mode selectable indoor unit.
Indoor unit without "Auto-RUN" mode
Indoor unit with two or three step of air flow setting
Indoor unit with only one of air flow setting
Indoor unit with automatically swing louver
Indoor unit without automatically swing louver
Indoor unit with three step of air flow setting
Indoor unit with two step of air flow setting

Item

[Flow of function setting]

Note 3: As for plural indoor unit, set indoor functions to each master and slave indoor unit. 

But only master indoor unit is received the setting change of indoor unit function “05 EXTERNAL INPUT” and “06 PERMISSION /

PROHIBISHION”.

Indoor unit No. are indicated only when 
plural indoor units are connected.

01

02

Validate setting of ESP:External Static Pressure

Invalidate setting of ESP

Automatical operation is impossible

Temperature setting button is not working

02

03

03

04

04

05

05

06

06

07

07

08

09

08

10

09

11

10

12

11

13

12

13

14

14

15

16

15

17

18

19

Consult the technical data etc. for each control details

Finalize : Press “

” (SET) button.

Reset

: Press “

” (RESET) button.

Select : Press                 button.
End

: Press ON/OFF  button.

It is possible to finish above setting on the way, 
and unfinished change of setting is unavailable.

” : Initial settings

” : Automatic criterion

How to set function

2.

1.

3.

4.

5.

It is possible to finish by pressing  ON/OFF  button on the way, but unfinished change of setting is 

unavailable.
During setting, if you press              (RESET) button, you return to the previous screen.
Setting is memorized in the control and it is saved independently of power failure.

Permission/prohibition control of operation will be valid.

Record and keep the

setting

The functional setting

Stop air-conditioner and press

          (SET) +           (MODE) buttons

at the same time for over three seconds.

Function

setting

Function

setting

Mode button is not working

On/Off button is not working

Fan speed button is not working

Louver button is not working

Timer button is not working

Remote thermistor is not working.
Remote thermistor is working.
Remote thermistor is working, and to be set for pro3.0˚C increase in temperature.
Remote thermistor is working, and to be set for pro2.0˚C increase in temperature.
Remote thermistor is working, and to be set for pro1.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -1.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -2.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -3.0˚C increase in temperature.

If you change the range of set temperature, the indication of set temperature 

will vary following the control.

If you change the range of set temperature, the indication of set temperature

will not vary following the control, and keep the set temperature.

If you change the remote controller function "14                        ", 

you must change the indoor function "04                      " accordingly. 

You can select the louver stop position in the four.

The louver can stop at any position.

In normal working indication, indoor unit temperature is indicated instead of airflow.
(Only the master remote controller can be indicated.)

Heating preparation indication should not be indicated.

Temperature indication is by degree C
Temperature indication is by degree F

To set other indoor unit, press

AIRCON

 NO.  button, which 

allows you to go back to the indoor 
unit selection screen 
(for example: I/U 000     ).

ON/OFF  button

(finished)

The filter sign is indicated after running for 180 hours.
The filter sign is indicated after running for 600 hours.
The filter sign is indicated after running for 1000 hours.
The filter sign is indicated after running for 1000 hours, then the indoor unit will be stopped by 
compulsion after 24 hours.
If you change the indoor function "04                           ",
you must change the remote controller function "14                         " accordingly.
You can select the louver stop position in the four.
The louver can stop at any position.

With the VRF series, it is used to stop all indoor units connected with the same outdoor unit immediately.
When stop signal is inputed from remote on-off terminal "CNT-6", all indoor units are stopped immediately. 

To be reset for pro3.0˚C increase in temperature during heating.
To be reset for pro2.0˚C increase in temperature during heating.
To be reset for pro1.0˚C increase in temperature during heating.

To be reset pro2.0˚C increase in return air temperature of indoor unit.
To be reset pro1.5˚C increase in return air temperature of indoor unit.
To be reset pro1.0˚C increase in return air temperature of indoor unit.

To be reset producing -1.0˚C increase in return air temperature of indoor unit.
To be reset producing -1.5˚C increase in return air temperature of indoor unit.
To be reset producing -2.0˚C increase in return air temperature of indoor unit.

When heating thermostat is OFF, fan speed is low speed.
When heating thermostat is OFF, fan speed is set speed.

When heating thermostat is OFF, fan speed is operated intermittently.
When heating thermostat is OFF, the fan is stopped.
When the remote thermistor is working, "FAN OFF" is set automatically.
Do not set "FAN OFF" when the indoor unit's thermistor is working.

Drain pump is run during cooling and dry.
Drain pump is run during cooling, dry and heating.
Drain pump is run during cooling, dry, heating and fan.
Drain pump is run during cooling, dry and fan.

After cooling is stopped or cooling thermostat is OFF, the fan does not perform extra operation.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for half an hour.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for an hour.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for six hours.

After heating is stopped or heating thermostat is OFF, the fan does not perform extra operation.
After heating is stopped or heating thermostat is OFF,the fan perform extra operation for half an hour.
After heating is stopped or heating thermostat is OFF,the fan perform extra operation for two hours.
After heating is stopped or heating thermostat is OFF, the fan perform extra operation for six hours.

During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes 
with low fan speed after twenty minutes' OFF.
During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes 
with low fan speed after five minutes' OFF.

Connected “OA Processing” type indoor unit, and is automatically defined.

Working only with the Single split series.
To control frost prevention, the indoor fan tap is raised. 

Change of indoor heat exchanger temperature to start frost prevention control.

How to check the current setting

When you select  from "No. and funcion" and press set button by the previous operation,  the "Setting" displayed first is the current 
setting.
(But, if you select "ALL UNIT      ", the setting of the lowest number indoor unit is displayed.)

Stop air-conditioner and press              (SET)              (MODE) 
buttons at the same time for over three seconds, and the 
"FUNCTION SET      " will be displayed.

Press              (SET) button.

Selecct "     FUNCTION      "  (remote control function) or "I/U 
FUNCTION     " (indoor unit function).

Operation message
Function description:      , 
setting description:

Function No.

Fixing button

Finishing button

7

2

1

Starting button

Previous screen button

Indoor unit selection button

Start

: Stop air-conditioner and press “

” (SET) and

” (MODE) buttons at the same time for over three seconds.

(Remote controller function)

(Indoor unit function)

In case of Single split series, by connecting ventilation device to CNT of the 

indoor printed circuit board (in case of VRF series, by connecting it to CND of the

indoor printed circuit board),  the operation of ventilation device is linked with the 

operation of indoor unit.

In case of Single split series, by connecting ventilation device to CNT of the indoor printed 

circuit board (in case of VRF series, by connecting it to CND of the indoor printed circuit 

board),  you can operate /stop the ventilation device independently by

    (VENT) button.

Press              (SET) button.

6.

"DATA LOADING" (Indication with blinking)

Display is changed to "01                       ".

7.

"DATA LOADING" (Blinking for 2 to 23 seconds to read the data)

(1)

(2)

(3)

Press              (SET) button.

On the occasion of remote control function selection

On the occasion of indoor unit function selection

Press         or         button.
"No. and function"are indicated by turns on the remote control 
function table, then you can select from them.
(For example)

Press         or         button.
Select the setting.

Press         or         button.

Select the setting.

The current setting of selected function is indicated.
(for example) "AUTO RUN ON"       If "02 AUTO RUN SET" is 
selected

Press              (SET) button.

Press              (SET) button.

Press         or         button.

Press         or         button.

Select the number of the indoor unit you are to set
If you select "ALL UNIT      ", you can set the same setting with 
all unites.

Press              (SET) 
"SET COMPLETE" will be indicated, and the setting will be 
completed.
Then after "No. and function" indication returns, Set as the 
same procedure if you want to set continuously ,and if to 
finish, go to 7.

Press   ON/OFF   button.
Setting is finished.

Indication is changed to "02 FAN SPEED SET".
Go to      .

[Note]

If plural indoor units are connected to a remote control,  the 
indication is "I/U 000" (blinking)       The lowest number of the 
indoor unit connected is indicated.

"No. and function" are indicated by turns on the indoor unit function 
table, then you can select from them.
(For example)

The current setting of selected function is indicated.
(For example) "STANDARD"       If "02 FAN SPEED SET" is 
selected.

Press              (SET) button.

"SET COMPLETE" will be indicated, and the setting will be 
completed.
Then after "No. and function" indication returns, set as the same 
procedure if you want to set continuously , and if to finish, go to 7.

Setting

Function No.
Function

When plural indoor units are connected to a remote control, press 
the   AIRCON NO.  button, which allows you to go back to the 
indoor unit selection screen. (example "I/U 000     ")

The initial function setting for typical using is performed automatically by the indoor unit connected, when remote 
controller and indoor unit are connected.
As long as they are used in a typical manner, there wiil be no need to change the initial settings.
If you would like to change the initial setting marked “

”, set your desired setting as for the selected item.

The procedure of functional setting is shown as the following diagram.

Function No.
Function

Setting

If you input signal into CNT of the indoor printed circuit board from external, the

indoor unit will be operated independently according to the input from external.

If you input into CNT of the indoor printed circuit board from external, all units which 

connect to the same remote controller are operated according to the input from external.

16

17

Airflow of fan becomes the three speed of         -        -        or         -        -        -        .

Airflow of fan becomes the two speed of         -        .

Airflow of fan becomes the two speed of         -        .

Airflow of fan is fixed at one speed.

Note2: Fan setting of "HIGH SPEED"

Initial function setting of some indoor unit is "HIGH SPEED".

UH - Hi 

UH - Me

UH - Hi - Me 

STANDARD

HIGH

SPEED1, 2

FAN

SPEED

SET

Hi - Lo

Hi - Me

-

-

-

-

-

-

-

Hi - Me - Lo

UH - UH - Hi - Me

UH - Hi - Me - Lo

Indoor unit air flow setting

Fan tap

PJA012D730

Summary of Contents for 25ZMX-S

Page 1: ...TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONERS Split system air to air heat pump type SRK20ZMX S 25ZMX S 35ZMX S 50ZMX S 60ZMX S Manual No 13s SRK T 144D DRAFT ...

Page 2: ...RANGE OF USAGE LIMITATIONS 22 7 CAPACITY TABLES 5 PIPING SYSTEM 19 24 8 APPLICATION DATA 9 OPTION PARTS 44 7IRED REMOTE CONTROL 2 3UPER LINK BOARD 3 NTERFACE KIT 3 56 10 TECHNICAL INFORMATION NSTALLATION OF INDOOR UNIT NSTALLATION OF OUTDOOR UNIT 28 How to read the model name Example SRK 20 ZMX Series code Inverter type Product capacity Cooling capacity 2 0kW Model name SRK Wall mounted type SRC O...

Page 3: ...ypropylene net washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless remote control Room temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipments Compressor overheat protection Overcurrent protection Fros...

Page 4: ...lene net washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless remote control Room temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipments Compressor overheat protection Overcurrent protection Frost prot...

Page 5: ...ene net washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless remote control Room temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipments Compressor overheat protection Overcurrent protection Frost prote...

Page 6: ...lene net washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless remote control Room temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipments Compressor overheat protection Overcurrent protection Frost prot...

Page 7: ...lene net washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless remote control Room temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipments Compressor overheat protection Overcurrent protection Frost prot...

Page 8: ...installation and service when viewing from the front Unit 15 Service space Service space Service space Terminal block Wired remote control Option Notes 1 The model name label is attached on the underside of the panel 2 It takes the interface kit SC BIKN E to connect the wired remote controller Unit mm Wireless remote control Hole on wall for right rear piping Hole on wall for left rear piping Gas ...

Page 9: ... I I I Open 250 80 280 I I I 280 Open 80 75 Examples of Dimensions installation I V 180 Open 80 Open Notes 1 It must not be surrounded by walls on the four sides 2 The unit must be fixed with anchor bolts An anchor bolt must not protrude more than 15mm 3 Where the unit is subject to strong winds lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction ...

Page 10: ... surrounded by walls on the four sides 2 The unit must be fixed with anchor bolts An anchor bolt must not protrude more than 15mm 3 Where the unit is subject to strong winds lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction 4 Leave 1m or more space above the unit 5 A wall in front of the blower outlet must not exceed the units height 6 The model...

Page 11: ... 10 13 SRK T 144D 3 Remote control Unit mm 60 26 167 ...

Page 12: ...ellow Y Color Mark t Th2 1 Th2 2 Th3 LM 1 LM 2 SM FM I Heat exch sensor Humidity sensor 50 60 only Fan motor Room temp sensor Flap motor Th1 Th2 Th3 Diode stack DS Fuse F FM I Terminal block T Louver motor LM 1 2 SM DS 1 2 Limit switch LS Inlet motor IM Description Item Varistor Va t t TO OUTDOOR UNIT HEAT EXCHANGER 1 2 N 3 POWER WIRES SIGNAL WIRE 1 2 N 3 Power source 1 Phase 220 240V 50Hz T IM Va...

Page 13: ...ould be chosen along the regulations in each country The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2 For an installation falling outside of these conditions please follow the internal cabling regulations Adapt it to the regulation in effect in each country 20 Model MAX running...

Page 14: ...ption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2 For an installation falling outside of these conditions please follow the internal cabling regulations Adapt it to the regulation in effect in each country 15 2 0 18 1 5 50 60 1 5mm x 3 2 Power cable indoor outdoor connecting wires Model MAX running current Power cable size 2...

Page 15: ...0 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N40 N60 N70 N20 N30 Cooling Heating Condition ISO T1 JIS C 9612 Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position 0 8m 1m Unit Mike position Center Low points Mike position at highest nois...

Page 16: ...7 dB A Heating 47 dB A 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N40 N60 N70 N20 N30 Cooling Heating Condition ISO T1 JIS C 9612 Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position 0 8m 1m Unit Mike position Center Low points Mike ...

Page 17: ...dB standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position 0 8m 1m Unit Mike position Center Low points Mike ...

Page 18: ...dB A Cooling Heating Condition ISO T1 JIS C 9612 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 Mike ...

Page 19: ...dB standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid Octave Band frequency Hz Sound Pressure Level dB standard 2 10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position 0 8m 1m Unit Mike position Center Low points Mike ...

Page 20: ...s TH2 Heat exchanger sensor TH1 EEV Capillary tube Heat exchanger Accumulator Strainer Models SRK20ZJX S 25ZJX S 35ZJX S Indoor unit Outdoor unit Flare connection Flare connection Liquid pipe φ6 35 Gas pipe φ9 52 Service valve Heat exchanger Heat exchanger sensor Electronic expansion valve Liquid Strainer Muffler Capillary tube Outdoor air temp sensor Muffler Muffler Compressor Accumulator Dischar...

Page 21: ...ation Approximately 15 to 46 D B Heating operation Approximately 15 to 24 D B Refer to the selection chart Selection chart Correct the cooling and heating capacity in accordance with the conditions as follows The net cooling and heating capacity can be obtained in the following way Net capacity Capacity shown on specification Correction factors as follows 1 Coefficient of cooling and heating capac...

Page 22: ...osting on outdoor heat exchanger during heating How to obtain the cooling and heating capacity Piping length m Cooling Heating 7 1 0 1 0 10 0 99 1 0 15 0 975 1 0 20 0 965 1 0 25 0 95 1 0 30 0 935 1 0 Air inlet temperature of outdoor unit in CWB Adjustment coefficient 15 0 95 0 95 0 94 0 93 0 91 0 88 0 86 0 87 0 92 1 00 10 9 7 5 3 1 1 3 5 or more ZMX S ZMX S ...

Page 23: ...2 22 2 11 2 36 2 24 2 55 2 42 2 64 2 50 2 70 2 54 2 85 2 70 2 96 2 67 34 2 15 2 04 2 29 2 18 2 49 2 36 2 58 2 45 2 64 2 51 2 79 2 65 2 91 2 65 35 2 12 2 01 2 26 2 14 2 46 2 33 2 55 2 42 2 61 2 48 2 77 2 63 2 89 2 65 36 2 08 1 98 2 22 2 11 2 43 2 30 2 52 2 39 2 58 2 45 2 74 2 60 2 86 2 64 38 2 01 1 91 2 15 2 04 2 36 2 24 2 46 2 34 2 52 2 39 2 69 2 55 2 81 2 60 39 1 97 1 88 2 11 2 01 2 33 2 21 2 43 ...

Page 24: ...ot conducted continuously Note 1 These data show the case where the operation frequency of a compressor is fixed Cooling only 2 Capacities are based on the following conditions 2 Corresponding refrigerant piping length 7m 2 Level difference of Zero 3 Symbols are as follows TC Total cooling capacity kW SHC Sensible heat capacity kW HC Heating capacity kW Indoor air temperature Indoor air temperatur...

Page 25: ...manual t Locations where the unit is exposed to chimney smoke t Locations at high altitude more than 1000m high t Locations with ammonic atmospheres t Locations where heat radiation from other heat source can affect the unit t Locations without good air circulation t Locations with any obstacles which can prevent inlet and outlet air of the unit t Locations where short circuit of air can occur in ...

Page 26: ...n of installation board Drilling of holes and fixture of sleeve Option parts Level position 2 locations Mating mark for level surface Fixing on concrete wall Use of nut anchor Use of bolt anchor Shaping of pipings Taping of the exterior Pipings Drain hose Top Nut M6 Mounting board Mounting board Max 10 Thickness of the wall 1 5cm 5 ø65 Indoor side Outdoor side Indoor side Outdoor side Installed st...

Page 27: ...6 35 ø9 52 ø12 7 0 0 0 5 0 0 0 5 0 0 0 5 1 0 1 5 1 0 1 5 1 0 1 5 1 5 2 0 1 5 2 0 2 0 2 5 Measurement B mm Clutch type Wing nut type CAUTION Do not apply excess torque to the flared nuts Otherwise the flared nuts may check depending Arrange the drain hose in a downward angle Avoid the following drain piping Pour water to the drain pan located under the heat exchanger and ensure that the water is di...

Page 28: ...Insert batteries Close the cover 1 2 3 Setting an indoor unit 1 2 3 Turn off the power supply and turn it on after 1 minute Point the wireless remote control that was set according to the procedure described on the left side at the indoor unit and send a signal by pressing the ACL switch on the wireless remote control Since the signal is sent in about 6 seconds after the ACL switch is pressed poin...

Page 29: ...circuit t Tighten the flare nut by torque wrench with specified method If the flare nut were tightened with excess torque this may cause burst and refrigerant leakage after a long period t Do not open the service valves for liquid line and gas line until completed refrigerant piping work air tightness test and evacuation If the compressor is operated in state of operation service valves before com...

Page 30: ... without good air circulation Locations with any obstacles which can prevent inlet and outlet air of the unit Locations where short circuit of air can occur in case of multiple units installation Locations where strong air blows against the air outlet of outdoor unit Locations where something located above the unit could fall It can cause remarkable decrease in performance corrosion and damage of ...

Page 31: ...rces A place where stringent regulation of electric noises is applicable Where it is safe for the drain water to be discharged Where noise and hot air will not bother neighboring residents Where snow will not accumulate Where strong winds will not blow against the outlet pipe A place where no TV set or radio receiver is placed within 1m If electrical interference is caused seek a place less likely...

Page 32: ... a side cover and remove to the front A B Flared pipe end A mm ø6 35 ø9 52 ø12 7 Copper pipe outer diameter 0 A 04 9 1 13 2 16 6 ø6 35 ø9 52 ø12 7 Copper pipe outer diameter 0 0 5 1 0 1 5 Copper pipe protrusion for flaring B mm In the case of a rigid clutch type With an R410A tool With a conventional tool CAUTION Do not apply force beyond proper fastening torque in tightening the flare nut Tighten...

Page 33: ... R410A Handle Hi Vacuum pump Vacuum pump adapter Anti reverse flow type Designed specifically for R410A Charge hose Designed specifically for R410A Check joint 0 1MPa 76cmHg Handle Lo Service valve Service valve Liquid side Service valve cap Service valve cap Service valve cap tightening torque N m Check joint blind nut tightening torque N m ø6 35 1 4 ø9 52 3 8 ø12 7 1 2 20 30 25 35 10 12 Service ...

Page 34: ...pply cables use conduits Do not lay electronic control cables wireless remote control and signaling wires and other cables together outside the unit Laying them together can result in the malfunctioning or a failure of the unit due to electric noises Fasten cables so that may not touch the piping etc When cables are connected make sure that all electrical components within the electrical component...

Page 35: ...h leakage circuit breaker h t r a E h t r a E Power supply Indoor unit Outdoor unit When wire length exceeds 30m use 2 5mm 2 wires Model SRC ZM S Model SRC ZMX S N L D1 D2 D3 C D1 D2 D3 Safety breaker 16A Earth leakage circuit breaker Power supply DRED Outdoor unit 1 2 N 3 1 2 N 3 Indoor unit When wire length exceeds 30m use 2 5mm 2 wires Model SRC ZMA S Model SRC ZMXA S Model DXC ZMA S C Connecti...

Page 36: ...e Does the existing pipe system to reuse satisfy all of the following 1 The pipe length is 30m or less 2 The pipe size conforms to the table of pipe size restrictions 3 The elevation difference between the indoor and outdoor units conforms to the following restrictions Where the outdoor unit is above 15m or less Where the outdoor unit is below 15m or less Which of the following refrigeration oils ...

Page 37: ... nut by torque wrench with specified method If the flare nut were tightened with excess torque this may cause burst and refrigerant leakage after a long period t Do not open the service valves for liquid line and gas line until completed refrigerant piping work air tightness test and evacuation If the compressor is operated in state of operation service valves before completed connection of refrig...

Page 38: ...ulation Locations with any obstacles which can prevent inlet and outlet air of the unit Locations where short circuit of air can occur in case of multiple units installation Locations where strong air blows against the air outlet of outdoor unit Locations where something located above the unit could fall It can cause remarkable decrease in performance corrosion and damage of components malfunction...

Page 39: ... A place where the unit can be kept away 5m or more from TV set and or radio receiver in order to avoid any radio or TV interference A place where good air circulation can be secured and enough service space can be secured for maintenance and service of the unit safely A place where the unit will not be affected by electromagnetic waves and or high harmonic waves generated by other equipment A pla...

Page 40: ...r and remove to the front A B Flared pipe end A mm ø6 35 ø12 7 Copper pipe outer diameter 0 A 04 9 1 16 6 ø6 35 ø12 7 Copper pipe outer diameter 0 0 5 1 0 1 5 Copper pipe protrusion for flaring B mm In the case of a rigid clutch type With an R410A tool With a conventional tool CAUTION Do not apply force beyond proper fastening torque in tightening the flare nut Tightening angle Tightening torque N...

Page 41: ...gned specifically for R410A Compound pressure gauge Pressure gauge Gauge manifold Designed specifically for R410A Handle Hi Vacuum pump Vacuum pump adapter Anti reverse flow type Designed specifically for R410A Charge hose Designed specifically for R410A Check joint 0 1MPa 76cmHg Handle Lo Service valve Service valve Liquid side Service valve cap Service valve cap Service valve cap tightening torq...

Page 42: ...together can result in the malfunctioning or a failure of the unit due to electric noises t Fasten cables so that may not touch the piping etc t When cables are connected make sure that all electrical components within the electrical component box are free of loose connector coupling or terminal connection and then attach the cover securely Improper cover attachment can result in malfunctioning or...

Page 43: ...nal connections Grounding terminals are provided in the control box N L 1 2 N 3 1 2 N 3 Safety breaker 16A Earth leakage circuit breaker h t r a E h t r a E Power supply Indoor unit Outdoor unit Model SRC ZMX S N L D1 D2 D3 C D1 D2 D3 Safety breaker 16A Earth leakage circuit breaker Power supply DRED Outdoor unit 1 2 N 3 1 2 N 3 Indoor unit Model SRC ZMXA S C Connecting cable between outdoor unit ...

Page 44: ...s OK Remove Check whether an existing pipe system is reusable or not by using the following flow chart Are not there any loose pipe supports Are there any branch pipes with no indoor unit connected NO Please consult with our distributor in the area if you need to recover refrigerant and charge it again Any combinations of pipe sizes not listed in the table are not usable If you obtain a negative f...

Page 45: ... case with a nipper or knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote control cord to the terminal block Connect the terminal of remote control X with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagr depending on the pulling out direction The wiring inside the remote...

Page 46: ...ontrol cord or center upper part nipper or knife n screws Connect the remote control cord to the terminal block Connect the terminal of remote control X Y with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagram depending on the pulling out direction The wiring inside the remote control case should be within 0 3mm2 recommended to 0 5mm2 The sheath ...

Page 47: ...CTION SET 2 Press button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER LIMIT by using button 5 Press SET button to fix 6 When UPPER LIMIT is selected valid during heating Press SET button to fix Indication example UPPER 26 C Displayed for two seconds After the fixed upper limit value displayed for two seco...

Page 48: ...on 04 accordingly You can select the louver stop position in the four The louver can stop at any position In normal working indication indoor unit temperature is indicated instead of airflow Only the master remote control can be indicated Heating preparation indication should not be indicated Temperature indication is by degree C Temperature indication is by degree F ON OFF button finished Start S...

Page 49: ... 5 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 5 C increase in return air temperature of indoor unit To be reset producing 2 0 C increase in return air temperature of indoor unit When heating thermostat is OFF fa...

Page 50: ...e indoor unit and is automatically defined it series ndoor fan tap is raised er temperature to start frost prevention control How to check the current setting When you select from No and funcion and press set button by the previous operation the Setting displayed first is the current setting But if you select ALL UNIT the setting of the lowest number indoor unit is displayed Stop air conditioner a...

Page 51: ...autions Before use please read these Safety Precautions thoroughly before installation All the cautionary items mentioned below are important safety related items to be taken into consideration so be sure to observe them at all times Incorrect installation could lead to serious consequences such as death major injury or envirommental destruction Symbols used in these precautions After completed in...

Page 52: ... unit approximately 1 8m Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the punch outs for the connection cables running into the casing with cutter Recess the electrical box procured locally and connection cables in the wall Mount the lower casing of the interface to the electric...

Page 53: ... external remote control unit procured locally to CNT terminal In case of the pulse input switch OFF the DIP switch SW2 1 on the interface PCB When setting operation permission prohibition mode switch OFF the DIP switch SW2 3 on the interface PCB Connection of super link E board Functions of CNT connector Switch ON the DIP switch SW2 2 Factory setting ON on the interface PCB Wiring connection betw...

Page 54: ...all the wired remote control with reference to the attached instruction manual of wired remote control B 0 3mm2 x 2 core cable should be used for the wiring of wired remote control C Maximum length of wiring is 600m If the length of wiring exceeds 100m change the size of cable as mentioned below 100m 200m 0 5mm2 x 2 core 300m or less 0 75mm2 x 2 core 400m or less 1 25mm2 x 2 core 600m or less 2 0m...

Page 55: ... 54 13 SRK T 144D WARING CAUTION 3 Super link E board SC ADNA E F ...

Page 56: ... 55 13 SRK T 144D ...

Page 57: ...ting limit COPd 2 40 Declared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20㷄 and outdoor temperature Tj temperature 20㷄 and outdoor temperature Tj Tj 2㷄 Pdh kW Tj 2㷄 COPd Tj 7㷄 Pdh kW Tj 7㷄 COPd Tj 12㷄 Pdh kW Tj 12㷄 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit ...

Page 58: ...Pd 2 40 Declared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20㷄 and outdoor temperature Tj temperature 20㷄 and outdoor temperature Tj Tj 2㷄 Pdh kW Tj 2㷄 COPd Tj 7㷄 Pdh kW Tj 7㷄 COPd Tj 12㷄 Pdh kW Tj 12㷄 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared...

Page 59: ...Pd 2 40 Declared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20㷄 and outdoor temperature Tj temperature 20㷄 and outdoor temperature Tj Tj 2㷄 Pdh kW Tj 2㷄 COPd Tj 7㷄 Pdh kW Tj 7㷄 COPd Tj 12㷄 Pdh kW Tj 12㷄 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared...

Page 60: ...Pd 2 70 Declared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20㷄 and outdoor temperature Tj temperature 20㷄 and outdoor temperature Tj Tj 2㷄 Pdh kW Tj 2㷄 COPd Tj 7㷄 Pdh kW Tj 7㷄 COPd Tj 12㷄 Pdh kW Tj 12㷄 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared...

Page 61: ...Pd 2 50 Declared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20㷄 and outdoor temperature Tj temperature 20㷄 and outdoor temperature Tj Tj 2㷄 Pdh kW Tj 2㷄 COPd Tj 7㷄 Pdh kW Tj 7㷄 COPd Tj 12㷄 Pdh kW Tj 12㷄 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared...

Page 62: ...itioning Refrigeration Systems 16 5 Konan 2 chome Minato ku Tokyo 108 8215 Japan http www mhi co jp Copyright MITSUBISHI HEAVY INDUSTRIES LTD Because of our policy of continuous improvement we reserve the right to make changes in all specifications without notice C ...

Reviews: