
–
11
–
(b)
Cooling
→
Heating
(i)
Start conditions
• When the outdoor unit operation mode is changed from the cooling operation to heating operation
(ii)
Control contents
1) When the compressor is operating, it makes the compressor stopped.
2) Each functional component operates according to the sequence shown below.
(iii)
End conditions
• End of sequence
• Meaning of marks
CM
Heating
15 seconds
3 minutes
Initial speed
Normal control
Initial opening
Cooling
Any state
FMo1, FMo2
20S
EEVH
EEVSC
OFF
Fully open
Fully closed
Fully closed
Time
Start conditions established
OFF
ON
Any state
Any state
CM
Compressor
EEVH
Heating electronic expansion valve
FMo1, FMo2 Fan motor
EEVSC
Subcooling coil electronic expansion valve
20S
4-way solenoid valve
―
―――
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...