'14 • KX-SM-202
9) 3 outdoor units combination use (Model 1200, 1250, 1300, 1350)
Master unit Slave unit Slave unit
CM01
CM11
(CM1)
CM21
(CM1)
(CM1)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM0 starts initially.
System load range
0
1
2
3
Local load range
0
1
1
1
Master unit
CM0
0rps
20−112rps
31−65rps
31−120rps
Slave unit CM
0rps
0rps
31−65rps
31−120rps
Slave unit CM
0rps
0rps
0rps
31−120rps
10) 3 outdoor units combination use (Model 1425, 1450, 1500, 1560, 1620, 1680)
Master unit Slave unit Slave unit
CM01
CM11
(CM1)
(CM1)
CM02
CM12
(CM2)
CM21
(CM1)
CM22
(CM2)
(CM2)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM0 starts initially.
System load range
0
1
2
3
Local load range
0
0
1
1
2
Master
unit
CM0
0rps
20−112rps
31−112rps
31−112rps
31−120rps
CM0
0rps
0rps
0rps
0rps
31−120rps
Slave
unit
CM
0rps
0rps
31−112rps
31−112rps
31−120rps
CM
0rps
0rps
0rps
0rps
31−120rps
Slave
unit
CM
0rps
0rps
0rps
31−112rps
31−120rps
CM
0rps
0rps
0rps
0rps
31−120rps
(ii) Rotation of compressor start/stop order
) The compressors will be changed over by determinating the start/stop order in each heat load zone.
) In case of single use, the starting order of CM and CM will be changed over on each occasion when the out-
door unit stops.
) In case of combination use, the starting order of CM0(CM)
〔
CM
〕
and CM0(CM)
〔
CM
〕
will be
changed over on each occation when the master unit or slave unit stops all independently.
) In case of combination use, the starting order of master and slave units will be changed over on each occasion
when the master unit or slave unit stops all independently.
Starting order of outdoor units
Master→Slave→Master