7
Mode
1
2
3
4
External input signal setting
Do not use external input. (Factory setting)
Emergency stop/Normal operation signal
(level signal)
ON/OFF signal (level signal)
ON/OFF and Prohibit/Permit remote
controller operation signal (pulse signal)
Notes
-
When the units are not operating after receiving an emergency stop signal,
the ON/OFF operation from the local remote controller will not be allowed,
and the ON/OFF and Prohibit/Permit settings on the Touch Controller
cannot be changed. Timer operation will not function.
ON/OFF operation from the local remote controller will not be allowed, and
the ON/OFF and Prohibit/Permit settings on the Touch Controller cannot
be changed. Timer operation will not function.
The ON-signal pulse width should be set to a value between 0.2 and 1
seconds.
6 Using external input/output
1. External signal input (CN2)
*To use external input, an external input/output adapter (PAC-YT41HAA; sold separately) is required.
(1) External input
Using external dry contact signals, the following operation of all air conditioning units can be controlled from the Touch Controller:
Emergency stop/Normal operation, ON/OFF, Permit/Prohibit local remote controller operation. These settings are made on the
External Input Settings on the Initial Settings screen that is accessible from the Service Menu screen. (Refer to Chapter 3 in the Initial
Setting Manual.)
(3) External input specifications
(A) Level signal
• tIf the type of signal assigned to the external input contact is "Emergency/Normal," the units in normal operation will stop
when
the signal input changes from OFF to ON. Conversely, the units that are stopped will resume normal operation when the signal
changes from ON to OFF. After the emergency stop is reset, the original operating status of each air conditioning unit will not be
automatically restored. The air conditioning units must be started up manually.
•
If the type of signal assigned to the external input contact is
"ON/OFF,"
the units that are stopped will start operation after the
input signal changes from OFF to ON. Conversely, the units that are in operation will stop after the input signal changes from
ON to OFF.
(B) Pulse signal
• If the incoming signal is the same as the signal that is currently being received, no status change will occur.
•
If local remote controller operation is prohibited, ON/OFF status, operation mode, or temperature setting cannot be changed and
filter sign cannot be reset from the remote controller.
• The ON-signal pulse width should be set to a value between 0.2 and 1 seconds.
(4) Sample circuit recommended
(A) Level signal
(B) Pulse signal
(2) Level signal and pulse signal
CN2
1
2
3
4
5
Lead wire
Green
Yellow
Orange
Red
Brown
Emergency stop/Normal
operation signal (level signal)
Emergency stop/Normal
operation signal input
Not used
Not used
Not used
Built-in 5 VDC power for external input * Exclusively for use with external input. Not usable for other purposes.
ON/OFF level signal
ON/OFF signal input
Not used
Not used
Not used
ON/OFF, Prohibit/Permit remote
controller operation (pulse signal)
ON signal input
OFF signal input
Prohibit-local-remote-controller-
operation signal input
Permit-local-remote-controller-
operation signal input
(ex.)ON/OFF
Signal 1 (ON)
Signal 2 (OFF)
*Same for Prohibit/Permit remote controller operation.
OFF
Contact ON
Contact OFF
OFF
ON
Normal
operation
Contact ON
Contact OFF
Normal
operation
Emergency
stop
Contact ON
Contact OFF
OFF
Contact ON
Contact OFF
OFF
ON
0.2 to 1 seconds
0.2 to 1 seconds
(A) Level signal
(B) Pulse signal
CN2
ON/OFF
or Emergency stop
Green
Yellow
X1
Touch Controller
Maximum
10 m
(32 ft)
X1
X1 X2 Y1 Y2
1
2
3
4
5
ON
OFF
Permit
Prohibit
CN2 Green
Yellow
X1
Touch Controller
Maximum
10 m
(32 ft)
Orange
X2
Red
Y1
Y2
Brown
1
2
3
4
5
Field supplied
Field supplied