REFRIGERANT CHARGE
The air conditioner is supplied with a minimum R410A refrigerant charge.
Refrigerant must be charged.
The following table shows the refrigerant charge that
must be introduced for the air conditioner only. Remote condenser, connections pipes and optional are excluded.
VERSION (1)
U / O
U / O
U / O
U / O
U / O
MODEL
011 P1 S
014 P1 S
016 P1 S
020 P1 S
022 P1 S
SIZE
E1
E2
E2
E3
E3
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
Refrigerant circuits x Refrigerant charge (2)
n x kg
1 x 3,2
1 x 3,4
1 x 3,4
1 x 4,0
1 x 4,0
HFC R410A - F Gas - CO
2
equivalent
t
6,68
7,10
7,10
8,35
8,35
VERSION (1)
U / O
U / O
U / O
U / O
U / O
MODEL
026 P1 S
032 P1 S
037 P1 S
041 P1 S
045 P1 S
SIZE
E3
E4
E4
E4
E4
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
Refrigerant circuits x Refrigerant charge (2)
n x kg
1 x 4,0
1 x 5,7
1 x 5,7
1 x 8,6
1 x 8,6
HFC R410A - F Gas - CO
2
equivalent
t
8,35
11,90
11,90
17,96
17,96
VERSION (1)
U / O
U / O
U / O
U / O
U / O
MODEL
039 P2 D
048 P2 D
055 P2 D
062 P2 D
075 P2 D
SIZE
E5
E5
E6
E6
E7
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
Refrigerant circuits x Refrigerant charge (2)
n x kg
2 x 4,5
2 x 4,5
2 x 4,9
2 x 4,9
2 x 8,1
HFC R410A - F Gas - CO
2
equivalent
t
18,79
18,79
20,46
20,46
33,83
VERSION (1)
U / O
U / O
U / O
U
U
MODEL
082 P2 D
092 P2 D
102 P2 D
117 P4 D
146 P4 D
SIZE
E7
E8
E8
E9
E9
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
Refrigerant circuits x Refrigerant charge (2)
n x kg
2 x 8,1
2 x 8,7
2 x 8,7
2 x 10,8
2 x 10,8
HFC R410A - F Gas - CO
2
equivalent
t
33,83
36,33
36,33
45,1
45,1
1.
U = Under, downflow / O = Over, upflow
2.
Refrigerant charge required for the air conditioner only operation. Remote condenser, connections pipes and optional are excluded.
For air conditioners with double refrigerant circuit is indicated the number of circuits x the charge of a single circuit.