INSTALLATION
The series is particularly suitable for installation in Data Centre of medium / small size with constant load.
DOWNFLOW VERSION (Under)
Typical installation is on the perimeter.
The units are placed along the perimeter of the Data Center. Air suction from the top of the unit and air
delivery in the underfloor void.
The air distribution is achieved by special tiles placed in front of the racks row, forming cold aisle for air
diffusion. On the rear of the racks is expelled the hot then aspirated by the unit.
For an optimal installation is advisable to provide the cold aisle containment.
Some solutions provide a service corridor around the server rooms where to place the units. In this case, it
is necessary to provide the air intake plenum for each unit. With this solution, all the space in the Data
Center is available for the installation of racks.
UPFLOW VERSION (Over)
The type of installation is practically similar to the previous.
The only difference is that for the air distribution
in the Data Center is not used the raised floor but ducts in the ceiling.
The series is also suitable for installation in UPS, Batteries, Distribution rooms and in all service areas of
the Data Center that need a service of conditioning.
OPTIONAL
An extensive list of accessories allows the unit to adapt effectively to the real needs of the system, reducing
the time and cost of installation.
PRODUCT FEATURES AND BENEFITS
•
Dual Fluid System
: Two independent cooling systems: Chilled water coil; Direct expansion coil
•
Electronic expansion valve;
•
New plug fans with EC electric motors and impeller in composite material, which guarantees a
reduction of power consumption;
•
New fans electric motor that do not require maintenance;
•
Improvement of the control software with advanced control logic;
•
Single or double refrigerant circuit;
•
Air suction temperature up to 40°C
F-GAS DIRECTIVE
The units highlighted in this publication contain <HFC R410A [GWP
100
2088]> fluorinated
greenhouse gases.