■ Indoor units
Install in a room with a floor area of Amin or more, corresponding to refrigerant amount M (factory-charged refrig-
erant + locally added refrigerant).
* For the factory-charged refrigerant amount, refer to the spec nameplate or installation manual.
For the amount to be added locally, refer to the installation manual.
Install the indoor unit so that the height from the floor to the bottom of the indoor unit is h0;
for ceiling suspended, cassette and ceiling concealed: 2.2 m or more
* There are restrictions in installation height for each model, so read the installation manual for the particular unit.
Case 1: ceiling concealed
Ceiling concealed
h0
]
2.2 [m]
M [kg]
Amin [m²]
1.0
4
1.5
6
2.0
8
2.5
10
3.0
12
3.5
14
4.0
16
4.5
20
5.0
24
5.5
29
6.0
35
6.5
41
7.0
47
7.5
54
8.0
62
8.5
69
9.0
78
9.5
87