28
OCH709A
Has the operation stopped
during pump down?
Was the operation started with
the stop valve closed, and was
it opened during operation?
No
Yes
O Check of outdoor refrigerant circuit
The operation has stopped to prevent
the diesel explosion caused by air
trapped in the refrigerant circuit.
Close the stop valve, and disconnect
the power plug or turn the breaker
OFF. *
WARNING:
When opening or closing the valve
below freezing temperatures,
refrigerant may spurt out from the gap
between the valve stem and the valve
body, resulting in injuries.
The unit occasionally stops when the
stop valve is opened or closed during
operation. Open the stop valve and
start the cooling operation again.
Yes
No
The refrigerant gas amount may be
60% or less than the normal amount.
Identify where the gas is leaking from,
and fix the leak.
*
CAUTION : Do not start the operation again to prevent hazards.
N Check the defrost heater (base pan heater)
Check the following points before checking electric continuity.
1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 10-6.1.
2. Is the resistance of defrost heater normal? Refer to 10-4.
3. Does the heater protector remain conducted (not open)?
4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
Is there 208/230 VAC between CN722 and
(
SUZ-KA09/12NAHZ
)/CN601 and (
Other
models
) on the inverter P.C. board? Refer to 10-6.1.
Not the problem of the inverter P.C. board.
Replace the inverter P.C. board.
No
Yes
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read
32°F (0°C) or below, and let the defrost thermistor continue to read 30°F (-1°C) or below.
NOTE:
In case both thermistors are more than the above temperature, cool them with cold
water etc...