15
-
(1) Comfortable TIMER setting (ON TIMER)
If the TIMER is set at ON when the operation select switch is set at the cooling, or the cooling in auto mode operation is selected, the
comfortable TIMER starts and determines the starting time of next operation based on the initial value of 15 minutes and the relationship
between the room temperature at the setting time (temperature of room temperature sensor) and the setting temperature. (Max. 60
minutes)
Operation mode
Operation start time correction value (Min.)
3 < Room temp. – Setting temp.
1 < Room temp. – Setting temp. 3
Room temp. – Setting temp. 1
At cooling
+5
No change
–5
Notes (1) At 5 minutes before the ON TIMER time, operation starts regardless of the temperature of the room temperature sensor (Th1).
(2) This function does not actuate when the operation select switch is set at the dry as well as the dry in the auto mode.
However, the operation of item (1) above is performed during the dry in the auto mode.
(3) During the comfortable TIMER operation, both the RUN light and TIMER light illuminate and the TIMER light goes off after expiration of the TIMER, ON setting
time.
If the difference (= Room temperature – Setting tempera-
ture) is 4ºC, the correction value is found to be +5 min-
utes from the table shown above so that the starting time
of next operation is determined as follows:
15 min. e 5 min. = 20 min. earlier
Current operation
Correction value
start time
(Example) Cooling
Room temperature
Setting temperature
Start
TIMER operation
(time)
Temperature
setting (˚C)
SLEEP operation
4.6
TIMER operation
Pressing the SLEEP button causes the temperature to be controlled as shown in the following chart with respect to the set temperature.
+1.0
0
-1.0
0
1.0
2.0
(2)
Operation starting time
Time
Cooling
Corrects the starting time of next operation by
calculating the temperature difference.
·
Setting time
15 min.
10 min.
5 min.
earlier
earlier
earlier
(3)
OFF TIMER operation
The OFF TIMER can be set at a specific time (in 10-minute units) within a 24-hour period.
Summary of Contents for SRK19CIS
Page 2: ... 1 TECHNICAL MANUAL ...
Page 43: ... 42 MEMO ...
Page 44: ... 43 PARTS LIST INDOOR UNIT SRK19CIS SRK25CIS OUTDOOR UNIT SRC19CIS SRC25CIS ...
Page 45: ... 44 ...
Page 46: ... 45 ...
Page 47: ... 46 ...
Page 48: ... 47 ...
Page 49: ... 48 ...
Page 50: ... 49 ...
Page 51: ... 50 ...
Page 52: ... 51 ...
Page 53: ... 52 ...
Page 54: ... 53 ...
Page 55: ... 54 ...
Page 56: ... 55 ...
Page 57: ... 56 ...
Page 58: ... 57 ...
Page 59: ... 58 ...
Page 60: ... 59 ...
Page 61: ... 60 ...
Page 62: ... 61 ...
Page 63: ... 62 ...
Page 64: ... 63 ...
Page 65: ...ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST Manual No 09 SRK T 086 ...