31
-
Service Valve
(three-way valve)
Charge hose
(Designed specifically for R22)
Compound
pressure
gauge
Pressure
gauge
Gauge Manifold
(Designed specifically for R22)
Handle Hi.
Vacuum pump
Vacuum pump adapter
(Anti-reverse flow type)
(Designed specifically for R22)
Charge hose
(Designed specifically for R22)
Service Port
–0.1MPa
(–76cmHg)
Handle Lo
Service Valve
(two-way valve)
(3)
Air purge
(a)
Tighten all flare nuts in the pipings both indoor and outside will so as not to cause leak.
(b)
Connect service valve, charge hose, manifold valve and vacuum pump as is illustrated below.
(c)
(d)
Open manifold valve handle Lo to its full width, and perform vacuum or evacuation.
Continue the vacuum or evacuation operation for 15 minutes or more and check to see that the vacuum gauge reads – 0.1 MPa
(– 76 cmHg).
After completing vacuum operation, fully open service valve (Both gas and liquid sides) with hexagon headed wrench.
(f)
Check f
(e)
Detach the charge hoses, from the service port.
or possible leakage of gas in the connection parts of both indoor and outdoor.
Please use an anti-reverse flow type vacuum pump adapter so as to prevent vacuum pump oil from running back into the system.
Oil running back into an air-conditioning system may cause the refrigerant cycle to break down.
Additional refrigerant charge
When refrigerant piping exceeds 7m conduct additional refrigerant charge by weight after refrigerant piping completion.
Additional charge amount per meter = 10g/m
[Example]
How much amount of additional charge for 25m piping?
(25 – 7)m 10g/m = 180g
180g for additional charge
(4)
Insulation of connecting portion
(a)
Cover the connecting portion of the refrigerant piping with the pipe cover and seal them.
If neglecting to do so, moisture occurs on the piping and water will drip out.
(b)
Finishing and fixing
1)
Tie up the piping with wrapping tape, and shape it so
that it conforms to which the pipe is attached.
2)
Fix them with clamps as right figure.
Cover the exterior portion with cov-
ering tape and shape the piping so
it will match the contours of the
route that the piping to take. Also
fix the wiring and pipings to the
wall with clamps.
Insulation
Refrigerant piping
Electrical wiring
Covering tape
Drain hose
Tapping screw
Vinyl tape
To cover the connecting portion with
insulation materials, cut upper portion and
then seal it with insulation materials.
·
⳯
Summary of Contents for SRK19CIS
Page 2: ... 1 TECHNICAL MANUAL ...
Page 43: ... 42 MEMO ...
Page 44: ... 43 PARTS LIST INDOOR UNIT SRK19CIS SRK25CIS OUTDOOR UNIT SRC19CIS SRC25CIS ...
Page 45: ... 44 ...
Page 46: ... 45 ...
Page 47: ... 46 ...
Page 48: ... 47 ...
Page 49: ... 48 ...
Page 50: ... 49 ...
Page 51: ... 50 ...
Page 52: ... 51 ...
Page 53: ... 52 ...
Page 54: ... 53 ...
Page 55: ... 54 ...
Page 56: ... 55 ...
Page 57: ... 56 ...
Page 58: ... 57 ...
Page 59: ... 58 ...
Page 60: ... 59 ...
Page 61: ... 60 ...
Page 62: ... 61 ...
Page 63: ... 62 ...
Page 64: ... 63 ...
Page 65: ...ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST Manual No 09 SRK T 086 ...