background image

16

Error Code

Abnormal point and detection method 

Cause

Countermeasure

P9

Pipe temperature thermistor / Condenser 
/ Evaporator (TH5)

 The unit is in 3-minute resume protec-

tion mode if short/open of thermistor is 
detected. Abnormal if the unit does not 
get back to normal within 3 minutes. (The 
unit returns to normal operation, if it has 
been reset normally.)

 Constantly detected during cooling, 

drying, and heating operation (except 
defrosting)

  Short: 90°C or more
  Open: -40°C or less

 Defective thermistor 

characteristics

 Contact failure of  connector 

(CN29) on the indoor controller 
board (Insert failure)

 Breaking of wire or contact 

failure of thermistor wiring

 Temperature of thermistor is 

90°C or more or -40°C or less 
caused by defective refrigerant 
circuit.

 Defective indoor controller 

board

~

 

Check resistance value of thermistor.

 

For characteristics, refer to (P1) above.

 Check contact failure of  connector (CN29) 

on the indoor controller board. 

  Refer to 8-5.
  Turn the power on and check restart after 

inserting connector again.

 Operate in test run mode and check pipe 

<condenser/evaporator> temperature with 
outdoor controller circuit board. If pipe 
<condenser/evaporator> temperature is 
extremely low (in cooling mode) or high (in 
heating mode), refrigerant circuit may have 
defect.

 Operate in test run mode and check pipe 

<condenser/evaporator> temperature 
with outdoor control circuit board. If there 
is extreme difference with actual pipe 
<condenser/evaporator> temperature replace 
indoor controller board.

  There is no abnormality if none of above 

comes within the unit.

  Turn  the power off and on again to operate.

E0

or

E4

Remote controller transmission 
error(E0)/signal receiving error(E4)

 Abnormal if main or sub remote con-

troller cannot receive any transmission 
normally from indoor unit of refrigerant 
address “0” for 3 minutes.

  (Error code: E0)

 Abnormal if sub-remote controller could 

not receive for any signal for 2 minutes. 
(Error code: E0) 

 Abnormal if indoor controller board 

cannot receive normally any data from 
remote controller board or from other 
indoor controller board for 3 minutes. 
(Error code: E4)

 Indoor controller board cannot receive 

any signal from remote controller for 2 
minutes. (Error code: E4)

 Check disconnection or looseness of indoor 

unit or transmission wire of remote controller.

 Set one of the remote controllers “main”, if 

there is no problem with the action above.

 Check wiring of remote controller.

• Total wiring length: max. 500 m
  (Do not use cable × 3 or more)
• The number of connecting indoor units: 

max. 16 units

• The number of connecting remote 

controller: max. 2 units

When the above-mentioned problem of  ~

 

are not seen.

Diagnose remote controllers.

a) When “RC OK” is displayed, remote 

controllers have no problem. 

Turn the power off, and on again to check. 
If abnormality generates again, replace 
indoor controller board.

b) When “RC NG” is displayed, replace 

remote controller.

c) When “RC E3” or “ERC 00-66” is displayed, 

noise may be causing abnormality.

 Contact failure at transmission 

wire of remote controller

 All remote controllers are set 

as “sub” remote controller. In 
this case, E0 is displayed on 
remote controller, and E4 is 
displayed at LED (LED1, LED2) 
on the outdoor controller circuit 
board.

 Miswiring of remote controller
 Defective transmitting/receiving 

circuit of remote controller

 Defective transmitting/receiving 

circuit of indoor controller board 
of refrigerant address “0”

 Noise has entered into the 

transmission wire of remote 
controller.

In case of checking pipe temperature 

with outdoor controller circuit board, 

be sure to connect A-control service 

tool (PAC-SK52ST).

(

)

PL

 Abnormal refrigerant circuit

  During Cooling, Dry, or Auto Cooling 

operation, when the following are 
regarded as failures when detected for 
one second.

a) The compressor continues to run for 30 

or more seconds.

b) The liquid pipe temperature or the 

condense/evaporator temperature is 
75°C or more.

* These detected errors will not be 

cancelled until the power source is 
reset.

 Abnormal operation of 4-way 

valve

 Disconnection of or leakage in 

refrigerant pipes

 Air into refrigerant piping
 Abnormal operation (no 

rotation) of indoor fan

 · 

 

Defective fan motor.

 · 

 

Defective indoor control 
board. 

 Defective refrigerant circuit 

(clogging)

 When this error occurs, be sure to 

replace the 4-way valve.

 Check refrigerant pipes for disconnection or 

leakage.

 After the recovery of refrigerant, vacuum 

dry the whole refrigerant circuit.

 Refer to section 8-7.
 Check refrigerant circuit for operation.

 

* To avoid entry of moisture or air into 

refrigerant circuit which could cause 
abnormal high pressure, purge air in 
refrigerant circuit or replace refrigerant.

OCH493E

Summary of Contents for SLZ-KA25VAQ

Page 1: ...D EDITION E WIRED REMOTE CONTROLLER Option Indoor unit Model Name Service Ref SLZ KA25VAQ TH SLZ KA25VAQR1 TH SLZ KA25VAQ2 TH SLZ KA35VAQ TH SLZ KA35VAQR1 TH SLZ KA35VAQR2 TH SLZ KA50VAQ TH SLZ KA50VAQR1 TH SLZ KA50VAQR2 TH INDOOR UNIT Model name indication ON OFF TEMP PARTS CATALOG OCB493 Please void OCH493 REVISED EDITION D SLZ KA25VAQ SLZ KA25VAQ2 SLZ KA35VAQ SLZ KA50VAQ Revision Added connecta...

Page 2: ... We will not be held responsible for mechanical failure system malfunction unit breakdown or accidents caused by failure to follow the instructions 1 TECHNICAL CHANGES 2 REFERENCE SERVICE MANUAL 2 1 OUTDOOR UNIT S SERVICE MANUAL 2 2 TECHNICAL DATA BOOK Service Ref Service Manual No SUZ KA25 50VA3 TH A OCH511 OCB511 SUZ KA25 35 50VA2 TH OCH472 OCB472 SUZ KA25 35 50VA2 TH A OCH473 OCB473 SUZ KA25 35...

Page 3: ... ON OFF button This lamp lights up in green while the unit is in operation It blinks while the remote controller is starting up or when there is an error Press to save the setting Main display Press to change the operation mode Main menu Press to move the cursor down Press to return to the previous screen Main display Press to decrease temperature Main menu Press to move the cursor up Press to bri...

Page 4: ...ctions cannot be operated Maintenance Auto descending panel Auto descending panel Optional parts Up Down you can do Manual vane angle Use to set the vane angle for each vane to a fixed position Initial setting Main Sub When connecting two remote controllers one of them needs to be designated as a sub controller Clock Use to set the current time Main display Use to switch between Full and Basic mod...

Page 5: ...ction indica tor The indicator shows the direc tion of the outcoming airflow One Hour Only indicator Room Temperature display Shows the room temperature The room temperature display range is 8 39 The display blinks if the temperature is less than 8 or 39 or more Louver display Indicates the action of the swing louver Does not appear if the louver is not running Power On indicator Indicates that th...

Page 6: ... K h A A W kW A mm in mm in mm in kg dB A rpm k k k Electrical data Fan motor Special remarks Capacity Dimensions WHT BLK 407 BLK BLU 86 BLU YLW 30 BRN RED 165 UNIT 570 22 7 16 PANEL 650 25 9 16 UNIT 235 9 1 4 PANEL 20 13 16 UNIT 570 22 7 16 PANEL 650 25 9 16 UNIT 16 5 PANEL 3 WHT BLK 393 BLK BLU 164 BLU YLW 47 BRN RED 319 WHT BLK 393 BLK BLU 164 BLU YLW 47 BRN RED 319 SLZ KA50VAQ TH SLZ KA25VAQR1...

Page 7: ...ENCIES Hz SLZ KA50VAQ TH SLZ KA50VAQR1 TH SLZ KA50VAQR2 TH High Medium 39 SPL dB 34 LINE 50Hz NOTCH Low 30 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 μbar BAND CENTER FREQUENCIES Hz SLZ KA25VAQ TH SLZ KA25VAQR1 TH High Medium 37 SPL dB 31 LINE...

Page 8: ...Air outlet hole 301 301 377 377 650 650 V M V M V M Detail drawing of fresh air intake Ceiling surface Cut out hole W 73 4 Burring hole 3 W 2 8 hole W 100 118 25 1 2 0 1 2 0 Emergency operation switch cooling Emergency operation switch heating Operation lamp DEFROST STAND BY lamp WIRELESS PANEL Receiver SLZ KA50VAQ SLZ KA50VAQR1 SLZ KA50VAQR2 SLZ KA35VAQ SLZ KA35VAQR1 SLZ KA35VAQR2 SLZ KA25VAQ SLZ...

Page 9: ...9 9 WIRED REMOTE CONTROLLER Unit mm PAR 21MAA PAR 30MAA 130 120 83 5 19 5 19 120 120 46 46 83 5 Option OCH493E ...

Page 10: ...OL NAME I B INDOOR CONTROLLER BOARD INDOOR POWER BOARD 86 7 9 211 725 2661 211 725 5 027 6 7 211 725 7 50 1 CENTRALLY CONTROL 32 5 6833 32 5 6833 75 160 66 21 1 225 287 225 DRAIN PUMP DEW PREVENTION HEATER 6 7 0 5 1 23 5 7 21 6 7 3 7 2 1 02725 7 7 50 86 VANE MOTOR DRAIN PUMP DRAIN SENSOR TERMINAL BLOCK 1 225 287 225 211 7 1 1 TERMINAL BLOCK REMOTE CONTROLLER TRANSMISSION LINE TERMINAL BLOCK REMOTE...

Page 11: ...temperature thermistor TH1 Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refrigerant LIQUID pipe connection Flare SLZ KA25VAQ TH SLZ KA35VAQ TH SLZ KA50VAQ TH SLZ KA25VAQR1 TH SLZ KA35VAQR1 TH SLZ KA50VAQR1 TH SLZ KA25VAQ2 TH SLZ KA35VAQR2 TH SLZ KA50VAQR2 TH OCH493E ...

Page 12: ... Pipe temperature error E4 E5 Remote controller signal receiving error Errors detected by unit other than indoor unit outdoor unit etc The check code in the parenthesis indicates PAR 30MAA model Symptom Remarks Indoor outdoor unit communication error Transmitting error Outdoor unit Open short of outdoor unit thermistors Compressor overcurrent interruption When compressor locked Abnormal high disch...

Page 13: ...ndoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire short Note Operation is not possible for about 30 seconds after cancellation of function selection Correct operation For description of each LED LED1 2 3 provided on the indoor controller refer to the following table LED1 power for microprocessor Indicates whether control power is supplied Make sure that this LED is alwa...

Page 14: ...ure with remote controller in test run mode If pipe liquid temperature is extremely low in cooling mode or high in heating mode refrigerant circuit may have defect Check pipe liquid temperature with remote controller in test run mode If there is extreme difference with actual pipe liquid temperature replace indoor controller board Turn the power off and on again to operate after checking P4 Drain ...

Page 15: ...rying mode Check clogging of the filter Remove blockage Measure the resistance of fan motor s winding Measure the output voltage of fan s connector FAN on the indoor controller board The indoor controller board should be normal when voltage of AC 220 240V is detected while fan motor is connected Refer to 8 5 Check outdoor fan motor Check operating condition of refrigerant circuit Heating mode Chec...

Page 16: ...nnection or looseness of indoor unit or transmission wire of remote controller Set one of the remote controllers main if there is no problem with the action above Check wiring of remote controller Total wiring length max 500 m Do not use cable 3 or more The number of connecting indoor units max 16 units The number of connecting remote controller max 2 units When the above mentioned problem of are ...

Page 17: ... normally read from the nonvolatile memory of the indoor controller board Defective indoor controller board Replace indoor controller board The check code in the parenthesis indicates PAR 30MAA model E1 or E2 Remote controller control board Abnormal if data cannot be normally read from the nonvolatile memory of the remote controller control board Error code E1 Abnormal if the clock function of rem...

Page 18: ... because of some abnormality Once the water leakage abnormality is detected abnormality state will not be released until the main power is reset Drain pump trouble Drain defective Drain pump clogging Drain pipe clogging Open circuit of drain sensor side heater Contact failure of drain sensor connector Dew condensation on drain sensor Drain water trickles along lead wire Drain water waving due to f...

Page 19: ...g of refrigerant address for outdoor unit There is no unit corresponding to refrigerant address 0 Check the setting of refrigerant address for outdoor unit Set the refrigerant address to 0 For grouping control system under which 2 or more outdoor units are connected set one of the units to 0 Set refrigerant address using SW1 3 6 on outdoor controller circuit board 2 LED2 on indoor controller board...

Page 20: ... Connect to the indoor controller board CNDK between to 220 240V AC CN2S Connect to the indoor controller board CN2D between to 12 6 13 7V DC Pin CNSK Connect to the indoor controller board CNDK between to 220 240V AC CN2S Connect to the indoor controller board CN2D between to 12 6 13 7V DC Pin SLZ KA25VAQ2 TH SLZ KA35VAQR2 TH SLZ KA50VAQR2 TH OCH493E ...

Page 21: ...CN2L Connector LOSSNAY CN51 Centrally control Control signal 13V pulse input Operation indicator 13VDC Malfunction indicator 13VDC CN6V Vane motor output MV CN90 Connect to the wire less remote controller board CNB CN31 Drain sensor DS CN29 Condenser evaporator temperature thermistor TH5 CN21 Pipe temperature thermistor Liquid TH2 CN20 Room temperature thermistor TH1 CN22 Remote controller connect...

Page 22: ...Z KA25VAQ SLZ KA25VAQ2 Model ON OFF 1 2 3 4 5 ON OFF 1 2 3 4 5 ON OFF 1 2 3 4 5 SLZ KA35VAQ SLZ KA50VAQ Action by switch opration OFF Available Extra low Not available ON Not available Stop Available Dip switch Function SW3 1 SW3 2 SW3 3 SW3 4 SW3 5 Power failure automatic recovery Set temperature in heating mode 4 deg up Fan speed when the thermostat is OFF during heating mode SW3 function OFF ON...

Page 23: ...e between the terminals with a tester Coil wiring temperature 10 C 30 C Pipe temperature thermistor liquid TH2 Indoor fan motor MF Check method and criterion Parts name Normal KA25VAQ Normal WHT BLK BLK BLU BLU YLW BRN RED a a a 157 174Ω KA35VAQ KA25VAQ2 a a a 302 335Ω KA50VAQ a a a 293 324Ω 4 3k 9 6k Abnormal Abnormal Opened or short circuited Opened or short circuited Measure the resistance betw...

Page 24: ...5 2kΩ 30 C 4 3kΩ 40 C 3 0kΩ Thermistor R0 6 0kΩ 5 Fixed number of B 3390 2 Rt 6exp 3390 0 C 6 0kΩ 10 C 3 9kΩ 20 C 2 6kΩ 25 C 2 2kΩ 30 C 1 8kΩ 40 C 1 3kΩ 60 C 0 6kΩ Thermistor for lower temperature 1 273 t 1 273 1 273 t 1 273 Thermistor for drain sensor 0 10 20 30 40 50 20 10 0 10 20 30 40 50 Thermistor for lower temperature Temperature Resistance k 20 0 20 40 60 80 Thermistor for drain sensor Temp...

Page 25: ...Indoor controller board Distance between indoor controller board and relay must be within 10m Be sure to secure insulation material by tape etc 5 Green Yellow Orange Connector 5P Indoor unit side Multiple remote controller adapter PAC SA88HA E Be sure to secure insulation material by tape etc Installation at site CN51 on indoor unit board Red Brown 1 CN51 MB CN51 WHT 9 3 OPERATION IN CONJUNCTION W...

Page 26: ...onnector with the plastic tape Vane motor Horizontal vane Connector Unlocking button Vane motor 3 Set the vertical vane of the air outlet by hand slowly within the range in the table below Measured standard position of the grille Horizontal vane Specified range Up down airflow direction Horizontal 30 Downward 45 Downward 55 Downward 70 A 21 mm 25 mm 28 mm 30 mm The vanes can be set between 21mm an...

Page 27: ... intake grille knob 3 Removing the panel 1 Remove the air intake grille Refer to Procedure 1 Corner panel See Figure 2 1 Remove the screw of the corner 2 Slide the corner panel to the direction of the arrow and remove the corner panel Panel See Photo 2 1 Disconnect the connector that connects with the unit 2 Remove the 2 screws from the panel and loose another 2 screws which are fixed to the oval ...

Page 28: ...nd the fan 2 from the indoor controller board 6 Remove the 3 screws fixed to the piping cover and remove the piping cover See Photo 9 7 Remove the 6 screws fixed to the flat plate and remove the flat plate 8 Disconnect the lead wires to the direction of the fan motor and remove the 3 nuts of the fan motor Photo 5 6 Removing the drain pan 1 Remove the panel Refer to Procedure 3 2 Remove the room te...

Page 29: ...oto 9 from the heat exchanger and remove the heat exchanger 9 Removing the drain pump DP and drain sensor DS 1 Remove the panel Refer to Procedure 3 2 Remove the drain pan Refer to Procedure 6 3 Remove the 2 screws fixed to the control box cover and remove the control box cover 4 Remove the connectors of the CNP and the CN31 from the indoor controller board 5 Remove the 1 screw fixed to the cover ...

Page 30: ...ISED EDITION E Distributed in Oct 2012 No OCH493 REVISED EDITION D Distributed in Feb 2012 No OCH493 REVISED EDITION C Distributed in Dec 2011 No OCH493 REVISED EDITION B Distributed in Mar 2011 No OCH493 REVISED EDITION A Distributed in Dec 2010 No OCH493 Made in Japan New publication effective Sep 2013 Specifications are subject to change without notice ...

Reviews: