8-4. FIXING HORIZONTAL VANE
Horizontal vane of each air outlet can be fixed according to the environment where it is installed.
Setting procedure
1) Turn off a main power supply (Turn off a breaker).
2) Remove the vane motor connector in the direction of the arrow shown below with pressing the unlocking button as in the
figure below.
Insulate the disconnected connector with the plastic tape.
Vane motor
Horizontal vane
Connector
Unlocking button
Vane motor
3) Set the vertical vane of the air outlet by hand slowly within the range in the table below.
Measured standard
position of the grille
Horizontal vane
Standard of
horizontal position
Dimension A (mm)
21
25
28
30
Level 30
°
(Min.)
Downward 45
°
Downward 55
°
Downward 70
°
(Max.)
w
Dimension between 21 mm and 30 mm can be arbitrarily set.
Caution
Do not set the dimension out of the range.
Erroneous setting could cause dew drips, smudge on ceiling or malfunction of unit.
<Set range>
.
OC320B-1.qxp 07.7.19 8:45 AM Page 26