7-1. CAUTIONS ON TROUBLESHOOTING
(1) Before troubleshooting, check the followings:
1
Check the power supply voltage.
2
Check that the indoor/outdoor connecting wire is correct.
(2) Take care of the followings during servicing.
1
Before servicing the air conditioner, be sure to turn off the remote controller first to stop the main unit, and then turn
off the breaker.
2
When removing the indoor controller board, hold the edge of the board with care NOT to apply stress on the
components.
3
When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wire
7-2. SELF-CHECK
7-2-1. Wired remote controller
7-2-2. Wireless remote controller
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1
Turn on the power.
2
Press the [CHECK] button twice.
3
Set address with [TEMP] button if system control is used.
4
Press the [ON/OFF] button to stop the self-check.
A
CHECK button
B
Address
C
TEMP. button
D
IC : Indoor unit
OC: Outdoor unit
E
Check code
F
Unit No.
G
Timer ON/OFF button
A
F
C
B
B
E
E
D
G
<To delete check code>
1
Display the error code on the self-check result display screen.
2
The address for self-check will blink when the
G
ON/OFF
button is pressed twice within 3 seconds.
– – – – : No trouble generated in the past.
F F F F : No corresponding unit.
ON/OFF
RESET
TOO
WARM
TOO
COOL
MODE
AUTO COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
h
24
23
56
24
[Procedure]
1
Turn ON the power.
2
While pressing both the MODE SELECT button and
TOO COOL button on the remote controller at the same
time, press the RESET button.
3
Firstly, release the RESET button.
4
And release the other 2 buttons since all LCD in
operation display section of the remote controller is
displayed after 3 seconds.
5
Transmit the signal of remote controller, pressing ON/ OFF
button on the remote controller.
(The above procedure allows OPERATION
INDICATOR lamp
to indicate the failure-mode.)
6
Transmit the signal of remote controller, pressing ON/ OFF
button to stop the self-check.