3. HEAT operation (Only SLH-1, 1.6, 2AR)
(1) Compressor control
1
3minute time delay
To prevent overload, the compressor will not start within 3minutes after stop.
2
The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or higher than the set temperature.
w
4degrees up control
During heat operation, lower the room temperature for 4degrees more than thermistor value.
3
The compressor stops in check mode.
4
Follow the item (5) during defrosting.
<HEAT operation time chart>
Minimum 3 minutes
W
2
ON
Thermostat
Indoor fan
Compressor
Outdoor fan
ON
LOW or MED. or HIGH
LOW or MED. or HIGH
VLo or
Lo or
OFF
VLo or
Lo or
OFF
VLo
OFF
OFF
ON
OFF
Operation starts by
P O W E R b u t t o n
ON.
Operation stops by
P O W E R b u t t o n
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
falls below set tem-
perature.
}
W
1
W
1
w
1 In case of coil temperature thermistor detect,
22°C or above : Lo notch
16°C ~ 22°C : VLo notch
15°C or below : FAN STOP
w
2 Even if the room temperature falls below the set temperature during this period, the compressor will not start until this period has
ended.
ON/OFF
RESET
TOO
WARM
TOO
COOL
MODE
AUTO COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
SLH-1AR
SLH-1.6AR
SLH-2AR
<How to operate>
1
Press POWER ON / OFF button.
2
Press MODE SELECT button to set operation mode to HEAT.
Each time the MODE SELECT button is pressed the display “
▲
” on the remote
controller moves.
3
Press the SET TEMPERATURE button to set the desired temperature.
NOTE: The set temperature changes 1°C when the
▲
or
▼
button is
press one time heating 17 to 28°C.