.  Test run

OPERATION 
INDICATOR 
lamp blinking 
pattern

Beep

Beep

Beep

Beep

Beep

Beep

Beep

Off

Approx. 2.5 sec.

On

Approx. 3 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

Off

Approx. 2.5 sec.

On

Approx. 3 sec.

On

0.5 sec.

On

0.5 sec.

· · · Repeated

Number of blinks/beeps in pattern indicates the check 
code in the following table (i.e., n=5 for “U2”)

Number of blinks/beeps in pattern indicates 
the check code in the following table 

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check 
starts
(Start signal 
received)

Beeper sounds

[Output pattern B]

OPERATION 
INDICATOR 
lamp blinking 
pattern

Beep

Beep

Beep

Beep

Beep

Beep

Beep

Off

Approx. 2.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

Off

Approx. 2.5 sec.

On

0.5 sec.

On

0.5 sec.

· · · Repeated

Number of blinks/beeps in pattern indicates the check 
code in the following table (i.e., n=5 for “P5”)

Number of blinks/beeps in pattern indicates 
the check code in the following table 

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check 
starts
(Start signal 
received)

Beeper sounds

•  Refer to the following tables for details on the check codes. (Wireless remote controller)
[Output pattern A]

[Output pattern A]  Errors detected by indoor unit

Wireless remote controller

Wired remote 

controller 

Symptom

Remark

  Beeper sounds/OPERATION

INDICATOR lamp blinks 

(Number of times)

Check code

1

P1

Intake sensor error

2

P2

Pipe (TH2) sensor error

P9

Pipe (TH5) sensor error

3

E6, E7

Indoor/outdoor unit communication error

4

P4

Drain sensor error / Float switch connector open

5

P5

Drain pump error

PA

Forced compressor error

6

P6

Freezing/Overheating protection operation

7

EE

Communication error between indoor and outdoor units

8

P8

Pipe temperature error

9

E4

Remote controller signal receiving error

10

11

12

Fb

Indoor unit control system error (memory error, etc.)

14

PL

Refrigerant circuit abnormal

No sound

E0, E3

Remote controller transmission error

No sound

E1, E2

Remote controller control board error

No sound

– – – –

No corresponding

[Output pattern B]  Errors detected by unit other than indoor unit (outdoor unit, etc.)

Wireless remote controller

Wired remote 

controller 

Symptom

Remark

Beeper sounds/OPERATION

INDICATOR lamp blinks 

(Number of times)

Check code

1

E9

Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)

For details, check the LED 
display of the outdoor controller 
board.

2

UP

Compressor overcurrent interruption

3

U3, U4

Open/short of outdoor unit thermistors

4

UF

Compressor overcurrent interruption (When compressor locked)

5

U2

Abnormal high discharging temperature/49C worked/insufficient refrigerant

6

U1, Ud

Abnormal high pressure (63H worked)/Overheating protection operation

7

U5

Abnormal temperature of heat sink

8

U8

Outdoor unit fan protection stop

9

U6

Compressor overcurrent interruption/Abnormal of power module

10

U7

Abnormality of super heat due to low discharge temperature

11

U9, UH

Abnormality such as overvoltage or voltage shortage and abnormal 

synchronous signal to main circuit/Current sensor error

12

13

14

Others

Other errors (Refer to the technical manual for the outdoor unit.)

*1 If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come 

on, there are no error records.

*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm the self-check start signal was received, the speci

-

fied refrigerant address is incorrect.

•  On wireless remote controller
  The continuous buzzer sounds from receiving section of indoor unit.
  Blink of operation lamp
•  On wired remote controller
  Check code displayed in the LCD.

01_BH79D045K05_EN.indd   15

2012/09/18 (火)   午後 3:45:00

Summary of Contents for RP100

Page 1: ...ente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade exte rior antes de instalar o aparelho de ar condicionado INSTALLATI...

Page 2: ...he unit in an unusual environment If the air conditioner is in stalled in areas exposed to steam volatile oil including machine oil or sulfu ric gas areas exposed to high salt content such as the seaside the perform ance can be significantly reduced and the internal parts can be damaged Do not install the unit where combustible gases may leak be produced flow or accumulate If combustible gas accum...

Page 3: ...tuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in Fig 3 2 so center the main unit against the opening of ceiling ensuring that the respective opposite sides on all sides of the clearance between them becomes identical Use M10 3 8 suspension bolts Suspension bolts are to be procured at the field Install securely ensuring that there is ...

Page 4: ...iagram Figures given in parentheses represent the dimensions in case of installing optional multi function casement 1 In advance set the parts onto the suspension bolts in the order of the washers with insulation washers without insulation and nuts double Fit the washer with cushion so that the insulation faces downward In case of using upper washers to suspend the main unit the lower washers with...

Page 5: ...hen commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam in sulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surfac...

Page 6: ...2 Wrong piping K Air bleeder A Insulation 9 mm or more L Raised B Downward slope 1 100 or more M Odor trap Grouped piping D O D ø32 PVC TUBE H Downward slope 1 100 or more E Make it as large as possible I O D ø38 PVC TUBE for grouped piping 9 mm or more insulation F Indoor unit G Make the piping size large for grouped piping J Up to 85 cm 1 Connect the drain socket supplied with the unit to the dr...

Page 7: ...140 outdoor unit application Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m For 200 250 outdoor unit application Max 18 m If 2 5 mm2 used Max 30 m If 4 mm2 used and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 2 The 10 m wire is attached in the remote controller accessory Max 500 m 3 The figures are NOT always against the ground S3 terminal has DC 24 V...

Page 8: ... switch settings when using separate indoor unit outdoor unit power supplies only Indoor unit specifications Required Required Required 1 A breaker with at least 3 0 mm contact separation in each pole shall be provided Use earth leakage breaker NV The breaker shall be provided to ensure disconnection of all active phase conductors of the supply 2 Max 120 m 3 The 10 m wire is attached in the remote...

Page 9: ...roller can be operated easily Area in which the remote controller is beyond the reach of children Installation method Fig 6 5 1 Attach the remote controller holder to the desired location using 2 tapping screws 2 Place the lower end of the controller into the holder A Remote controller B Wall C Display panel D Receiver The signal can travel up to approximately 7 meters in a straight line within 45...

Page 10: ... Press the FILTER A and TEST RUN B buttons simultaneously for at least 2 seconds The function selection screen will disappear momentarily and the air conditioner OFF display will appear 2 For wireless remote controller Fig 6 10 Changing the power voltage setting Be sure to change the power voltage setting depending on the voltage used 1 Going to the function select mode Press the CHECK button F tw...

Page 11: ...vanes vanes angle setup 2 3 Ο 1 When the power supply returns the air conditioner will start 3 minutes later 2 Power failure automatic recovery initial setting depends on the connecting outdoor unit 6 3 3 How to set the fixed up down air direction Only for wired remote controller and PUHZ PU H application Only the particular outlet can be fixed to certain direction with the procedures below Once f...

Page 12: ...nward after it becomes fixed airflow direction mode Fixed airflow direction mode display Note 0 indicates all outlets MITSUBISHI ELECTRIC label Outlet No 4 Outlet No 2 Outlet No 3 Outlet No 1 Outlet No Unit No Up Down air direction Refrigerant address No To select and identify the outlet to set 1 Press Set Temperature button 5 to change number with the outlet No blinking Select outlet No to set 2 ...

Page 13: ...et No Up Down air direction Refrigerant address No Unit No Outlet No Up Down air direction Refrigerant address No Unit No Adjust to the next unit No with Set Temperature button 5 refrigerant address No 00 is remained 2 Press Filter button 3 to send the information on remote controller 3 Wait for 15 seconds How does the air conditioner run Only air from the outlet which No displayed on remote contr...

Page 14: ...ivate mode then check whether warm air is blown out from the unit 5 Press the FAN button and check whether fan speed changes 6 Press the VANE button and check whether the auto vane operates properly 7 Press the ON OFF button to stop the test run Note Point the remote controller towards the indoor unit receiver while following steps 2 to 7 It is not possible to run the TEST RUN in FAN DRY or AUTO m...

Page 15: ...r unit control system error memory error etc 14 PL Refrigerant circuit abnormal No sound E0 E3 Remote controller transmission error No sound E1 E2 Remote controller control board error No sound No corresponding Output pattern B Errors detected by unit other than indoor unit outdoor unit etc Wireless remote controller Wired remote controller Symptom Remark Beeper sounds OPERATION INDICATOR lamp bli...

Page 16: ... after power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once Incorrect wiring between indoor and...

Page 17: ... 9 2 2 Removing the corner panel Fig 9 4 Remove the screw from the corner of the corner panel Slide the corner panel as indicated by the arrow 1 to remove the corner panel Fig 9 3 Fig 9 4 A Intake grille B Grille C Intake grille levers D Grille hook E Hole for the grille s hook F Corner panel G Screw H Detail 3 Selection of the air outlets For this grille the discharge direction is available in 11...

Page 18: ...box of the unit 5 Installing the intake grille Fig Note When reinstalling the corner panels each with a safety wire attached con nect the other end of each safety wire to the grille using a screw 4 pcs 4 8 as shown in the illustration If the corner panels are not attached they may fall off while the unit is operating Perform the procedure that is described in 9 2 Preparing to attach the grille in ...

Page 19: ...Maintenance mode operation procedures 10 Easy maintenance function For PUHZ H RP application only By using the maintenance mode you can display many types of maintenance data on the remote controller such as the heat exchanger temperature and compressor current consumption for the indoor and outdoor units This function can be used whether the air conditioner is operating or not During air conditio...

Page 20: ...n the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC Only RP35 50 60 71 100 BH79D045K05 Printed in UNITED KINGDOM HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUS...

Reviews: