Changes the selection(No.).

Unit No.

"1-4"

Refrigerant address No.

"00-15"

Outlet No.

"1-4"or "0"

Up/Down air direction 

5 steps or

cancel

Press for 2 

seconds to

change / cancel

"Fixed airflow 

direction mode".

Press  the button with either refrigerant

address No., unit No. or outlet No. blinking, ...

Only the air conditioner with the No. on remote 

controller and its outlet are set to the setting 5 of

 the airflow direction. (Other outlets are closed.)

It is used to identify the air conditioner and 

outlet to set.

Press the button with 

Up/Down air direction indicater blinking, ... 

This is used only to decide direction conclusively.

Attention: Be careful not to set wrong air conditioner.

Attention

Only the air conditioner with the No. on Remote 

controller and its outlet are fixed at "Up/Down air 

direction" which is blinking.

PAR-21MAA

ON/OFF

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

Set temperature buttons

Down

Up

Mode button (Return button)

ON/OFF button

Fan Speed button

Filter

 button

(<Enter> button)

Check button (Clear button)

Resets the fixed airflow direction mode. 

Sends the information on

remote controller display. 

·Refer to the next page for details.

Moves between the selected(blinking)

parts.

Unit No.

Outlet No.

Up/Down air direction

Refrigerant address No.

6.  Electrical work

< Process for setting >

[1] To turn off air conditioner and change the remote 

     controller to "Fixed airflow direction mode"

1.Press ON/OFF button  

to turn off the air conditioner.

2.Press Fan Speed button 

2

 and Filter 

button 

for more than 2

   seconds simultaneously and it becomes the fixed airflow direction  

   mode after a while.  

Air blows downward after it becomes 
"fixed airflow direction mode".

"Fixed airflow direction mode" display

Note: "0" indicates

all outlets.

MITSUBISHI

ELECTRIC

label

Outlet No.4

Outlet No.2

Outlet No.3

Outlet No.1

Outlet No.

Unit No.

Up/Down air direction Refrigerant address No.

[] To select and identify the outlet to set

1.Press Set Temperature button 

5

 to change number with the outlet No. 

   blinking. Select outlet No. to set.

2.Press Filter 

button 

3

 to send the information on remote controller.

3. Wait for 15 seconds .  How does the air conditioner run?

   →Only the air from the selected outlet blows downward. 
          →Go to step[3].
   →Air from the wrong outlet blows downward. 
          →Repeat 1 and set again.
   →All outlets are closed. 
          →The numbers of the air conditioner (refrigerant address No., 
               Unit No.) are wrong. Refer to How to find air conditioner No..

[3] To fix air direction

1.Press Mode button (Return button) 

4

 to blink Up/Down air direction 

   indicater.

2.Press Set Temperature button 

5

 until the direction to set is chosen.

3.Press Filter 

button 

3

 to send the information on remote controller to

   air conditioner.

4.Wait for 15 seconds .  How does the air conditioner run?

   →Airflow direction is set in the selected direction. 
       →The fixed setting completed (Go to step [4].)
   →Airflow direction is set in the wrong direction.
       →Repeat 2. and set again.

Air direction changes 

This indicates NO FIXED SETTING(canceled) 

Unit No.  Outlet No. 

Refrigerant address No.

Up/Down air direction

[4] To cancel "Fixed airflow direction mode"

1.Press ON/OFF button 

1

 

to cancel "Fixed airflow direction mode".

   It is also canceled by pressing Fan Speed button 

2

 and Filter 

button 

   

3

 for more than 2 seconds simultaneously.

2.Do not operate remote controller for 30 seconds after the "Fixed airflow 

   direction mode" is canceled. It does not accept even if it is operated. 

Operation buttons (During the fixed airflow direction mode)

01_BH79D045K05_EN.indd   12

2012/09/18 (火)   午後 3:44:58

Summary of Contents for RP100

Page 1: ...ente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade exte rior antes de instalar o aparelho de ar condicionado INSTALLATI...

Page 2: ...he unit in an unusual environment If the air conditioner is in stalled in areas exposed to steam volatile oil including machine oil or sulfu ric gas areas exposed to high salt content such as the seaside the perform ance can be significantly reduced and the internal parts can be damaged Do not install the unit where combustible gases may leak be produced flow or accumulate If combustible gas accum...

Page 3: ...tuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in Fig 3 2 so center the main unit against the opening of ceiling ensuring that the respective opposite sides on all sides of the clearance between them becomes identical Use M10 3 8 suspension bolts Suspension bolts are to be procured at the field Install securely ensuring that there is ...

Page 4: ...iagram Figures given in parentheses represent the dimensions in case of installing optional multi function casement 1 In advance set the parts onto the suspension bolts in the order of the washers with insulation washers without insulation and nuts double Fit the washer with cushion so that the insulation faces downward In case of using upper washers to suspend the main unit the lower washers with...

Page 5: ...hen commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam in sulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surfac...

Page 6: ...2 Wrong piping K Air bleeder A Insulation 9 mm or more L Raised B Downward slope 1 100 or more M Odor trap Grouped piping D O D ø32 PVC TUBE H Downward slope 1 100 or more E Make it as large as possible I O D ø38 PVC TUBE for grouped piping 9 mm or more insulation F Indoor unit G Make the piping size large for grouped piping J Up to 85 cm 1 Connect the drain socket supplied with the unit to the dr...

Page 7: ...140 outdoor unit application Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m For 200 250 outdoor unit application Max 18 m If 2 5 mm2 used Max 30 m If 4 mm2 used and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 2 The 10 m wire is attached in the remote controller accessory Max 500 m 3 The figures are NOT always against the ground S3 terminal has DC 24 V...

Page 8: ... switch settings when using separate indoor unit outdoor unit power supplies only Indoor unit specifications Required Required Required 1 A breaker with at least 3 0 mm contact separation in each pole shall be provided Use earth leakage breaker NV The breaker shall be provided to ensure disconnection of all active phase conductors of the supply 2 Max 120 m 3 The 10 m wire is attached in the remote...

Page 9: ...roller can be operated easily Area in which the remote controller is beyond the reach of children Installation method Fig 6 5 1 Attach the remote controller holder to the desired location using 2 tapping screws 2 Place the lower end of the controller into the holder A Remote controller B Wall C Display panel D Receiver The signal can travel up to approximately 7 meters in a straight line within 45...

Page 10: ... Press the FILTER A and TEST RUN B buttons simultaneously for at least 2 seconds The function selection screen will disappear momentarily and the air conditioner OFF display will appear 2 For wireless remote controller Fig 6 10 Changing the power voltage setting Be sure to change the power voltage setting depending on the voltage used 1 Going to the function select mode Press the CHECK button F tw...

Page 11: ...vanes vanes angle setup 2 3 Ο 1 When the power supply returns the air conditioner will start 3 minutes later 2 Power failure automatic recovery initial setting depends on the connecting outdoor unit 6 3 3 How to set the fixed up down air direction Only for wired remote controller and PUHZ PU H application Only the particular outlet can be fixed to certain direction with the procedures below Once f...

Page 12: ...nward after it becomes fixed airflow direction mode Fixed airflow direction mode display Note 0 indicates all outlets MITSUBISHI ELECTRIC label Outlet No 4 Outlet No 2 Outlet No 3 Outlet No 1 Outlet No Unit No Up Down air direction Refrigerant address No To select and identify the outlet to set 1 Press Set Temperature button 5 to change number with the outlet No blinking Select outlet No to set 2 ...

Page 13: ...et No Up Down air direction Refrigerant address No Unit No Outlet No Up Down air direction Refrigerant address No Unit No Adjust to the next unit No with Set Temperature button 5 refrigerant address No 00 is remained 2 Press Filter button 3 to send the information on remote controller 3 Wait for 15 seconds How does the air conditioner run Only air from the outlet which No displayed on remote contr...

Page 14: ...ivate mode then check whether warm air is blown out from the unit 5 Press the FAN button and check whether fan speed changes 6 Press the VANE button and check whether the auto vane operates properly 7 Press the ON OFF button to stop the test run Note Point the remote controller towards the indoor unit receiver while following steps 2 to 7 It is not possible to run the TEST RUN in FAN DRY or AUTO m...

Page 15: ...r unit control system error memory error etc 14 PL Refrigerant circuit abnormal No sound E0 E3 Remote controller transmission error No sound E1 E2 Remote controller control board error No sound No corresponding Output pattern B Errors detected by unit other than indoor unit outdoor unit etc Wireless remote controller Wired remote controller Symptom Remark Beeper sounds OPERATION INDICATOR lamp bli...

Page 16: ... after power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once Incorrect wiring between indoor and...

Page 17: ... 9 2 2 Removing the corner panel Fig 9 4 Remove the screw from the corner of the corner panel Slide the corner panel as indicated by the arrow 1 to remove the corner panel Fig 9 3 Fig 9 4 A Intake grille B Grille C Intake grille levers D Grille hook E Hole for the grille s hook F Corner panel G Screw H Detail 3 Selection of the air outlets For this grille the discharge direction is available in 11...

Page 18: ...box of the unit 5 Installing the intake grille Fig Note When reinstalling the corner panels each with a safety wire attached con nect the other end of each safety wire to the grille using a screw 4 pcs 4 8 as shown in the illustration If the corner panels are not attached they may fall off while the unit is operating Perform the procedure that is described in 9 2 Preparing to attach the grille in ...

Page 19: ...Maintenance mode operation procedures 10 Easy maintenance function For PUHZ H RP application only By using the maintenance mode you can display many types of maintenance data on the remote controller such as the heat exchanger temperature and compressor current consumption for the indoor and outdoor units This function can be used whether the air conditioner is operating or not During air conditio...

Page 20: ...n the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC Only RP35 50 60 71 100 BH79D045K05 Printed in UNITED KINGDOM HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUS...

Reviews: