background image

3

GB

2. Refrigerant Oil Recovery Operation Flow

2.1 Refrigerant oil recovery operation monitor display

(*1) The initial remaining time that indicates the refrigerant oil recovery is 80. A countdown will start on step 3 in the cooling mode. 

The countdown does not include the time for checking the refrigerant charge amount.

(*2) S-1: Refrigerant oil recovery complete, S-0: Refrigerant oil recovery incomplete, 

r-1: Refrigerant charge adjustment complete, r-0: Refrigerant charge adjustment incomplete.

1. How to read the LED on the service monitor

Units' operation status can be monitored on the LED display by setting the dipswitches SW1-1 through 1-10 on the MAIN board of the 
outdoor units.
Four 7-segment LEDs are used to display numerical values, flags, and alphabets to display various information.

The LEDs display such information as pressure and temperature in numerical values and operating conditions and the ON/OFF status of 
solenoid valve as flags.

Display of numerical values

Example:When the pressure sensor reads 18.8 kg/cm

2

G (Item No. 58)

* The unit of pressure is in kg/cm

2

G.

* Use the following conversion formula to convert the displayed value into a value in SI unit (MPa).

SI unit (MPa) = Displayed value (kg/cm

2

G) 



0.098

Flag display (Each set of two lines in vertical alignment indicates a flag.)

Example:Outdoor unit in the 3-minute restart delay mode. (Item No. 14)

2. Table of items that can be monitored on the LED on the outdoor unit circuit board

No

SW1

Display content

LED display

Notes

1

2

3

4

5

6

7

8

9

10

LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 LD9 LD10

58

0

1

0

1

1

1

0

0

0

0

High  pressure  (kgf/cm

2

G)

-99.9 to 999.9

59

1

1

0

1

1

1

0

0

0

0

Low  pressure  (kgf/cm

2

G)

-99.9 to 999.9

60

0

0

1

1

1

1

0

0

0

0

Intermediate pressure
(kgf/cm

2

G)

-99.9 to 999.9

45

1

0

1

1

0

1

0

0

0

0

Discharge temperature (°C)

-99.9 to 999.9

131

1

1

0

0

0

0

0

1

0

0

Refrigerant oil recovery operation 

steps

rEP 

 steps

Reversed 

display

122

0

1

0

1

1

1

1

0

0

0

Refrigerant oil recovery 
remaining time

 (*1)

0 to 9999

120

0

0

0

1

1

1

1

0

0

0

Refrigerant oil recovery 

completion indicator flag

Refrigerant charge adjustment 

completion indicator flag

S-1 (0) 

 r-1 (0) 

(*2)

Reversed 

display

7SEG LED

LD1

LD2

LD3

LD4

LD5

LD6

LD7

LD8

WT06218X01_en.fm  Page 3  Tuesday, December 14, 2010  4:19 PM

Summary of Contents for REPLACE MULTI PURY-RP200YJM-B

Page 1: ...LLECTE D HUILE MINÉRALE RÉCUPÉRATION DE L HUILE FRIGORIFIQUE MANUAL DE INSTRUCCIONES PARA LA RECOGIDA DE ACEITE MINERAL RECUPERACIÓN DE ACEITE REFRIGERANTE RACCOLTA DELL OLIO MINERALE RECUPERO DELL OLIO REFRIGERANTE MANUALE DI ISTRUZIONI MANUAL DE INSTRUÇÕES DE RECOLHA DE ÓLEO MINERAL RECUPERAÇÃO DO ÓLEO REFRIGERANTE Air Conditioners For Building Application Outdoor Unit PURY RP200 250 300YJM B BS...

Page 2: ...ort to the refrigerant circuit Evacuation port high pressure side A port through which refrigerant for the indoor units is charged D Service port on the low pressure valve Connecting port to the refrigerant circuit Evacuation port low pressure side A port through which refrigerant for the indoor units is charged E A valve to be closed after the completion of refrigerant oil recovery operation BV3 ...

Page 3: ...hen the pressure sensor reads 18 8 kg cm2 G Item No 58 The unit of pressure is in kg cm2G Use the following conversion formula to convert the displayed value into a value in SI unit MPa SI unit MPa Displayed value kg cm2 G 0 098 Flag display Each set of two lines in vertical alignment indicates a flag Example Outdoor unit in the 3 minute restart delay mode Item No 14 2 Table of items that can be m...

Page 4: ... BC controllers To calculate the required amount of refrigerant charged for the pipes refer to 10 1 Calculation of additional refrigerant charge in the installation manual on the CD ROM If there is excess refrigerant that cannot be charged use it during oil recovery operation at step 4 cooling operation After charging the required amount of refrigerant to the existing pipes open the valve so that ...

Page 5: ...is insufficient the units may stop during refrigerant oil recovery or it may take longer than usual to complete a test run 5Setting the unit address and checking for proper system operation Set the unit address turn on the power and check for proper operation of the system If an attempt is made to operate the outdoor unit before the refrigerant oil recovery operation is complete an error code 7116...

Page 6: ...igerant charge Do not exceed the maximum amount If the refrigerant oil recovery operation does not finish after the maximum amount of refrigerant is charged close the valve on refrigerant cylinder and wait for the operation to be completed automatically If the cylinder runs out of refrigerant during the refrigerant oil recovery operation continue the operation and replace the cylinder I If more th...

Page 7: ...pswitches 3 1 and 4 8 to ON in that order S 0 r 0 The refrigerant oil recovery operation is not completed To restart the refrigerant oil recovery operation set the dipswitches 3 1 and 4 8 to ON in that order 8Disconnecting the cylinder After completing the oil recovery operation close the valve on the cylinder and disconnect the cylinder within five minutes 9Recording the amount of refrigerant tha...

Page 8: ...Electromagnetic Compatibility Directive 2004 108 EC Pressure Equipment Directive 97 23 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STAREET UXBRIDGE MIDDLESEX UB8 1QQ U K WT0621...

Page 9: ...s Replace Belfast PURY RP200 300YJM B Declaration of Conformity PURY RP200 300YJM B Installation Manual WT06216X01 PURY RP200 300YJM B Mineral Oil Collection Instruction Book WT06218X01 PURY RP200 300YJM B Parts Catalogue BWE1024B PURY RP200 300YJM B Service Manual HWE10140 Replace Multi VRF Data Book MEE15K060 PURY RP200 300YJM B Parts Catalogue BWE10240 ...

Page 10: ......

Reviews: