3
- 33
3.4 Buffer Memory
3.4.12 Warning output flag (Un\G48)
3
3.4.12 Warning output flag (Un\G48)
(1) When the digital input value falls outside CH Warning output upper/lower limit value
(Un\G86 to Un\G97) range, the bit corresponding to each channel turns to "1".
(2) Whether the warning is the upper or lower limit value warning can be checked on each
channel.
(3) If the warning is detected on any of the channels enabled for conversion, Warning out-
put signal (XE) turns on.
(4) Turning on Operating condition setting request (Y9) or Warning output clear request
(YE) clears Warning output flag.
(5) Refer to Section 3.2.3 for details of warning output function.
3.4.13 CH
[ ]
Scaling enable/disable setting (Un\G53)
(1) Set whether to enable or disable the scaling on each channel.
(2) To validate the settings, on/off of Operating condition setting request (Y9) is required.
(Refer to Section 3.3.2.)
(3) The default setting is all-channel scaling disable.
(4) Refer to Section 3.2.5 for details of warning output function.
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
1: Warning output
0: Normal
Un\G48
0
0
0
0
CH2 CH2 CH1 CH1
CH4 CH4 CH3 CH3
CH6 CH6 CH5 CH5
b12 to b15 information is fixed at 0
lower
limit
value
upper
limit
value
lower
limit
value
upper
limit
value
lower
limit
value
upper
limit
value
lower
limit
value
upper
limit
value
lower
limit
value
upper
limit
value
lower
limit
value
upper
limit
value
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH
2
CH
1
CH
4
CH
3
CH
6
CH
5
1: Scaling disable
0: Scaling enable
Un\G53
0
0
0
0
0
0
0
0
0
0
b6 to b15 information is fixed at 0
Summary of Contents for Q66DA-G
Page 2: ......
Page 6: ...A 4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 189: ......