67
OCH721A
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Pulse
LEV-A opening pulse on error occurring
0–480
0–480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 s 0.5 s 2 s
30
1
°F
[°C]
Indoor room temperature (TH1) on error
occurring
46–102
46–102 (8–39°C)
°F
[°C]
Indoor pipe temperature/Liquid (TH2) on
error occurring
−38–190
−38–190 (−39–88°C)
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
(Example) When −15˚F;
0.5 s 0.5 s 2 s
05
1
Indoor pipe temperature/Cond./Eva.
(TH5) on error occurring
−38–190
−38–190 (−39–88°C)
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
(Example) When –15˚F;
0.5 s 0.5 s 2 s
05
1
Outdoor pipe temperature/2-phase (TH6)
on error occurring
−38–190
−38–190 (−39–88°C)
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
(Example) When –15˚F;
0.5 s 0.5 s 2 s
05
1
Outdoor ambient temperature (TH7) on
error occurring
−38–190
−38–190 (−39–88°C)
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
(Example) When –15˚F;
0.5 s 0.5 s 2 s
05
1
Outdoor heat sink temperature (TH8) on
error occurring
−40–392
−40–392 (−40–200°C)
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100˚F or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
°F
[°C]
°F
[°C]
°F
[°C]
°F
[°C]