13
OCH707C
4
DATA
4-1. REFILLING REFRIGERANT CHARGE (R32: kg)
Additional charge is required for pipes longer
than 30 m.
Service Ref.
Piping length (one way)
Initial
charged
5 m
10 m
15 m
20 m
25 m
30 m
40 m
50 m
55 m
60 m
65 m
PUZ-M100VKA(-ET).TH
2.0
2.2
2.4
2.6
2.8
3.1
3.5
3.9
4.1
-
-
3.1
PUZ-M125VKA(-ET).TH
2.6
2.8
3.0
3.2
3.4
3.6
4.0
4.4
4.6
4.8
5.0
3.6
PUZ-M140VKA(-ET).TH
PUZ-M100YKA(-ET).TH
2.0
2.2
2.4
2.6
2.8
3.1
3.5
3.9
4.1
-
-
3.1
PUZ-M125YKA(-ET).TH
2.6
2.8
3.0
3.2
3.4
3.6
4.0
4.4
4.6
4.8
5.0
3.6
PUZ-M140YKA(-ET).TH
4-2. COMPRESSOR TECHNICAL DATA
(Winding temperature at 20°C)
Service Ref.
PUZ-M100VKA(-ET).TH
PUZ-M100YKA(-ET).TH
PUZ-M125/140VKA(-ET).TH
PUZ-M125/140YKA(-ET).TH
Compressor model
SVB220FBGMT
SVB220FBAMT
MVB33FBVMC
Winding
Resistance
(Ω)
U-V
0.95
1.64
0.88
U-W
0.95
1.64
0.88
W-V
0.95
1.64
0.88