Caution:
Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of
electric shock.
Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or
Þ
re.
Note:
This device is intended for the connection to a power supply system with a maximum permissible system impedance shown in the above table at the
interface point (power service box) of the user’s supply.
The user must ensure that this device is connected only to a power supply system which ful
Þ
ls the requirement above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.
This equipment complies with IEC 61000-3-12 provided that the short-circuit power S
SC
is greater than or equal to S
SC
(*2) at the interface point between
the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected only to a supply with a short-circuit power S
SC
greater than or equal to S
SC
(*2).
S
SC
(*2)
Model
S
SC
(MVA)
PURY-(E)P200YHM
1.14
PURY-(E)P250YHM
1.26
PURY-(E)P300YHM
1.57
PURY-P350YHM
2.00
PURY-P400YHM
2.12
12. Test run
12.1. The following phenomena do not represent faults.
Phenomenon
Display of remote controller
Cause
Indoor unit does not perform cooling
(heating) operation.
“Cooling (heating)”
ß
ashes
When another indoor unit is performing the heating (cooling) operation, the
cooling (heating) operation is not performed.
The auto vane rotates and begins to blow air
horizontally.
Normal display
If air has been blowing downward for 1 hour during cooling, the unit may
automatically change to horizontal blowing with the control operation of the
auto vane. During defrosting or immediately after heating start-up/shut-down,
the auto vane automatically rotates to blow air horizontally for a short period
of time.
Fan setting changes during heating.
Normal display
Ultra-low speed operation is commenced at thermostat OFF.
Light air automatically changes over to set value by time or piping temperature
at thermostat ON.
Fan stops during heating operation.
Defrost display
The fan is set to stop during defrosting.
Fan does not stop while operation has been
stopped.
No lighting
The fan is set to run for 1 minute after stopping to exhaust residual heat (only
in heating).
No setting of fan while start SW has been
turned on.
Heat ready
Ultra low-speed operation for 5 minutes after SW ON or until piping
temperature becomes 35°C, low speed operation for 2 minutes thereafter, and
then set notch is commenced (Hot adjust control).
Indoor unit remote controller shows “H0”
or “PLEASE WAIT” indicator for about
Þ
ve
minutes when turning ON universal power
supply.
“H0” or “PLEASE WAIT”
ß
ashes
The system is being started up.
Operate remote controller again after “H0” or “PLEASE WAIT” disappears.
Drain pump does not stop when unit is
stopped.
Light out
After cooling operation stops, the unit continues to operate drain pump for
three minutes and then stops it.
Drain pump continues to operate while unit
has been stopped.
Unit continues to operate drain pump if drainage is generated, even after the
unit has been stopped.
Indoor unit emits noise when switching from
heating to cooling and vice versa.
Normal display
This is a switching sound of the refrigerant circuit and does not imply a
problem.
Immediately after startup, the indoor unit
emits the sound of the refrigerant
ß
ow.
Normal display
Unstable
ß
ow of the refrigerant emits a sound. This is temporary and does not
imply a problem.
Warm air comes from an indoor unit that is
not performing a heating operation.
Normal display
The LEV is slightly open to prevent refrigerant, of the indoor unit that is not
performing the heating operation, from being lique
Þ
ed. This does not imply a
problem.
13. Information on rating plate
Model
P200
P250
P300
P350
P400
Unit combination
-
-
-
-
-
Refrigerant (R410A)
8.0kg
10.5kg
10.5kg
11.8kg
11.8kg
Allowable pressure (Ps)
HP: 4.15 MPa, LP: 2.21 MPa
Net weight
220kg
235kg
240kg
265kg
265kg
Model
P450
P500
P550
Unit combination
P250
P200
P250
P250
P300
P250
Refrigerant (R410A)
10.5kg
8.0kg
10.5kg
10.5kg
10.5kg
10.5kg
Allowable pressure (Ps)
HP: 4.15 MPa, LP: 2.21 MPa
Net weight
235kg
220kg
235kg
235kg
240kg
235kg
Model
P600
P650
P700
Unit combination
P300
P300
P350
P300
P400
P300
Refrigerant (R410A)
10.5kg
10.5kg
11.8kg
10.5kg
11.8kg
10.5kg
Allowable pressure (Ps)
HP: 4.15 MPa, LP: 2.21 MPa
Net weight
240kg
240kg
265kg
240kg
265kg
240kg
•
•
•
•
•