126
No.
SW1 setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678
1
2
3
4
5
6
7
8
52
00101
100
Outdoor LEV
-A
opening pulse
0–2000 (pulse)
Display of opening pulse of outdoor LEV
53
10101
100
Outdoor LEV
-A opening
pulse abnormality delay
54
01
101
100
Outdoor LEV
-A opening
pulse abnormality
55
11
101
100
Outdoor LEV
-B
opening pulse
56
0001
1100
Outdoor LEV
-B opening
pulse abnormality delay
57
1001
1100
Outdoor LEV
-B opening
pulse abnormality
58
0101
1100
63LS (Low pressure)
−99.9–999.9
(kgf/cm²)
Display of data from sensor and thermistor
59
1101
1100
63LS abnormality delay
−99.9–999.9
(kgf/cm²)
60
001
11
100
63 LS abnormality
61
101
11
100
TH2 (HIC pipe)
−99.9–999.9
(
:
)
62
011111
00
TH2(HIC) abnormality delay
−99.9–999.9
(
:
)
63
111111
00
TH2 (HIC) abnormality
64
00000010
Operational frequency
0–255 (Hz)
Display of actual operating frequency
65
10000010
Target frequency
0–255 (Hz)
Display of target frequency
66
01000010
Outdoor fan control
step number
0–15
Display of number of outdoor fan control steps (target)
69
10100010
IC1 LEV Opening pulse
0–2000 (pulse)
Display of opening pulse of
indoor LEV
70
01
100010
IC2 LEV Opening pulse
71
11
100010
IC3 LEV Opening pulse
72
00010010
IC4 LEV Opening pulse
73
10010010
IC5 LEV Opening pulse
74
01010010
High pressure sensor (Pd)
−99.9–999.9
(kgf/cm²)
Display detected data of outdoor unit sensors and thermistors
75
11010010
TH4(Compressor)(Td) data
−99.9–999.9
(
:
)
76
001
10010
TH6(Suction pipe) (ET) data
77
101
10010
TH7(Ambient) data
78
01
110010
TH3(Outdoor liquid pipe) data
80
00001010
TH8(Heat sink) data
81
10001010
IC1 TH23
(Gas)
−99.9–999.9
(
:
)
(When indoor unit is not connected, it is displayed as 0.)
Display detected data of indoor unit thermistor
82
01001010
IC2 TH23
(Gas)
83
11001010
IC3 TH23
(Gas)
84
00101010
IC4 TH23
(Gas)
85
10101010
IC5 TH23
(Gas)
OCH632A
Summary of Contents for PUMY-P112VKM3