8-5. INTERNAL SWITCH FUNCTION TABLE
PUMY-P112/125/140VKM3(-BS)
PUMY-P112/125/140YKM3(-BS)
PUMY-P112/125/140YKME3(-BS)
Switch
Step
Function
Operation in Each Switch Setting
Remarks
Purpose
Additional Information
ON
OFF
When to Set
SWU1 ones digit SWU2 tens digit
Rotary switch
Before turning the power ON
<Initial settings>
SW1 Digital Display Switch
1–8
Can be set either during operation or not.
<Initial settings>
T
o
display
outdoor
unit's
information
to
the LED on outdoor multi controller circuit board. Refer to "8-10. OUTDOOR UNIT
INFORMA
TION DISPLA
Y".
SW2 Function Switch
1
Selects operating system startup
With centralized controller
Without centralized controller
Before turning the power ON
<Initial settings>
Turn ON when the centralized controller is connected to the outdoor unit.
•
SW2-1 must be turned ON if a central controller is connected to the syst
em.
An example of this would
be
a TC-24,
EB50A, AG150, AE50
or AE200.
If SW2-1 is not turned on, while using a central controller
, in rare circumstances problems may be
encountered such as indoor units not responding to group commands.
Therefore, turning SW2-1 ON
is recommended if a central controller is used.
•
Group setting of 2 or more
A-IC units which
is connected to branch box via centrilized controller is not allowed.
2
Connection Information Clear Switch
Clear
Do not clear
When relocating units or connecting additional units.
—
3
Abnormal data clear switch input
Clear abnormal data
Normal
OFF to ON any time after the power is turned on.
To delete an error history
.
4
Pump down
Run adjustment mode
Normal
During compressor running
To facilitate outdoor unit the pumping down operation. Frequency = Fixed to 65 Hz
Indoor-Electronic expansion valve = Fully open
Outdoor fan step = Fixed to 10
Please refer to a section referring to the pumping down on outdoor units Installation Manuals. It might not be possible to collect all the refrigerant if the amount is excessive.
5
—
—
—
—
—
—
6
—
—
—
—
—
—
SW3 T
rial
operation
1
ON/OFF from outdoor unit*
1
ON
OFF
Any time after the power is turned ON.
<Initial settings>
—
—
2
Mode setting
Heating
Cooling
—
—
SW4/ SW8 Model Switch
1–6
MODEL
SELECTION 1:ON 0:OFF
Before the power is turned ON.
<Initial settings> Set for each capacity
.
—
—
SW5 Function switch
1
Demand control setting for
Australia
Aus
trali
a s
etting
Normal*
2
Can be set when of
f or during
operation
<Initial settings>
Turn ON to activate the demand control for Australia.
(Do not turn this ON if the unit is in outside
Australia)
2
Change
the
indoor
unit's
LEV
opening at start-up
Enable
Normal
To set the LEV opening at start-up higher than usua
l.
(+150 pulses) To improve the operation with the LEV almost clogged.
The refrigerant flow noise at start-up
become louder
.
3
—
—
—
—
—
—
4
—
—
—
—
—
—
5
Change
the
indoor
unit's
LEV
opening at defrost
Enable
Normal
Can be set when OFF or during operation
To set the LEV opening higher than usual during defrosting operation. (Only Qj
[
10 is valid, + 300 pulses)
To avoid the discharge temperature increase
and provide efficient defrosting operation.
The refrigerant flow noise during the
defrosting operation become louder
.
*
1
T
est run on PWFY
series cannot be run by the outdoor unit. Use a switch on the indoor unit or a remote controller to perform test run.
*
2
Refer to "8-6. OUTDOOR UNIT
INPUT/OUTPUT
CONNECT
OR".
SWU2
(tens digit)
0
1 2
3 4
5
67
89
SWU1
(ones digit
)
0
1 2
3 4
5
67
89
1
ON OFF
2
3
4
5
6
7
8
SW4
MODEL
PUMY
-P1
12VKM3
SW8
PUMY
-P125VKM3
PUMY
-P140VKM3
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
4
5
6
1
ON OFF
2
1
ON OFF
2
1
ON OFF
2
SW4
MODEL
PUMY
-P1
12YKM(E)3
SW8
PUMY
-P125YKM(E)3
PUMY
-P140YKM(E)3
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
4
5
6
ON OFF
1
ON OFF
2
1
ON OFF
2
1
ON OFF
2
1
2
3
4
5
6
SWU2
(tens digit)
0
1 2
3 4
5
67
89
SWU1
(ones digit
)
0
1 2
3 4
5
67
89
1
ON OFF
2
3
4
5
6
7
8
1
ON OFF
2
3
4
5
6
1
ON OFF
2
1
ON OFF
2
3
4
5
6
7
8
OCH632A
Summary of Contents for PUMY-P112VKM3
Page 157: ...157 OCH632A ...