62
Outdoor unit
Switch
SW U1
1s digit
SW U2
10ths digit
SW1 Digital
Display
Switching
SW2
Function
Switching
SW5
Function
switching
SW3 Trial
operation
SW4
Model
Switching
Step
Operation in Each Switch Setting
ON
OFF
When to Set
Remarks
Before turning
the power on
Before the power
is turned on.
Rotary switch
1
2
3
4
5
6
1
2
1
2
3
4
5
6
7
8
Function
1~8
1~6
Can be set
either during
operation or not.
Before turning the
power on
Any time after the
power is turned on.
OFF to ON any time after
the power is turned on.
During compressor
running
Before turning the
power on
OFF to ON during com-
pressor running.
Enable
—
ON
Disable
Enable
Enable
Active
Normal
Normal
Inactive
Heating
Enable
Enable
Cooling
OFF
—
—
Without centralized
controller
With centralized
controller
Clear
Do not clear
Normal
Normal
Normal
Normal
Fix
Normal
Fix
Normal
Clear abnormal data
Run adjustment mode
Selects operating system startup
Connection Information Clear Switch
Abnormal data clear switch input
Pump down
Auto change over from Remote controller
—
Mode setting
ON/OFF from outdoor unit
<Initial settings>
<Initial settings>
<Initial settings>
<Initial settings>
<Initial settings>
<Initial settings>
Set for each capacity.
Pressure limitation value change
Change the indoor unit's LEV opening at
start
Fixing the indoor units linear expansion
valve opening
Fix the operation frequency
Change the indoor unit's LEV opening
at defrost
SWU2
(10ths digit)
0 12
3
45
6
7
8
9
SWU1
(1s digit)
0 12
3
45
6
7
8
9
SWU2
(10ths digit)
0 12
3
45
6
7
8
9
SWU1
(1s digit)
0 12
3
45
6
7
8
9
1
ON
OFF
2 3 4 5 6 7 8
1
ON
OFF
2 3 4 5 6 7 8
1
ON
OFF
2 3 4 5 6
1
ON
OFF
2
Can be set when off
or during operation
Can be set when off
or during operation
Switching the target sub cool.
During the FAN or COOL mode,and thermo-OFF
or OFF in heating operation, set the opening of
linear expansion valve on indoor unit
+
1
During the FAN or COOL mode,and thermo-OFF
in heating operation, set the opening of linear ex-
pansion valve on indoor unit
+
2
Active
Inactive
+
1 SW5-7 Refrigerant amount shortage measure during heating operation
(Refrigerant piping is long etc.)
+
2 SW5-8 Countermeasure against room temperature rise for indoor unit in FAN, COOL, and thermo-OFF (heating) mode.
+
1 MODEL SELECT 1:ON 0:OFF
MODELS
PUMY-P100Y
PUMY-P125Y
PUMY-P140Y
1 1 0 0 1 0
1 2 3 4 5 6
SW4
1 1 0 0 0 1
1 1 0 0 1 1
MODELS
PUMY-P100V
PUMY-P125V
PUMY-P140V
0 1 0 0 1 0
1 2 3 4 5 6
SW4
0 1 0 0 0 1
0 1 0 0 1 1
1
ON
OFF
2 3 4 5 6 7 8
9-5. INTERNAL SWITCH FUNCTION TABLE
PUMY-P100VHMB(-BS) PUMY-P100VHMBR1(-BS) PUMY-P100VHMBR2(-BS)
PUMY-P125VHMB(-BS) PUMY-P125VHMBR1(-BS) PUMY-P125VHMBR2(-BS)
PUMY-P140VHMB(-BS) PUMY-P140VHMBR1(-BS) PUMY-P140VHMBR2(-BS)
PUMY-P100YHMB(-BS) PUMY-P100YHMBR1(-BS) PUMY-P100YHMBR2(-BS)
PUMY-P125YHMB(-BS) PUMY-P125YHMBR1(-BS) PUMY-P125YHMBR2(-BS)
PUMY-P140YHMB(-BS) PUMY-P140YHMBR1(-BS) PUMY-P140YHMBR2(-BS)
The black square (
■
) indicates a switch position.