35
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Plate HEX liquid pipe temperature (TH6)
– 39~88
:
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Condensing temperature (T
63HS
)
– 39~88
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
:
0~150
(When it is 100 Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 105 Hz;
0.5 secs. 0.5 secs. 2 secs.
Hz
Calculated maximum frequency
0~150
1
ON
2 3 4 5 6
:
Ambient temperature (TH7)
-39~88
-39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
Outdoor heatsink temperature (TH8)
-40~200
:
-40~200
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
(When the thermistor detects 100
:
or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
1
ON
2 3 4 5 6
°C
Discharge superheat (SHd)
0~255
Cooling and Heating: SHd = TH4-T
63HS
0~255
(When the SHd is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
1
ON
2 3 4 5 6
Outdoor unit setting information
Code
display
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P / Cooling only
Single phase / 3 phase
Display details
0 : H·P 1 : Cooling only
0 : Single phase 2 : 3 phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
(Example) When heat pump, 3 phase and defrosting
(normal) are set up, “20” is displayed.
1
ON
2 3 4 5 6
Water inlet temperature (TH32)
0~100
:
0~100
1
05