8. Special Function

8.1. Low noise mode (on-site modifi cation) (Fig. 8-1)

The low noise mode will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.
•  

The ability varies according to the outdoor temperature and conditions, etc.

1

  Complete the circuit as shown when using the external input adapter  

(PAC-SC36NA). (Option)

2

  SW1 ON: Low noise mode

 

SW1 OFF: Normal operation

A

  Circuit diagram example (low noise mode)

B

 On-site arrangement

C

  External input adapter (PAC-SC36NA)

D

 

Outdoor unit control board

E

 

Max. 10 m

Fig. 8-1

7

Summary of Contents for PUHZ-W85VHA

Page 1: ...εγκατάστασης της εσωτερικής μονάδας προτού εγκαταστήστε τη μονάδα MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade interior antes de instalar a unidade INSTALLATIONSMANUAL Læs af sikkerhedshensyn denne vejledning samt monteringsvejledningen til indendørsenheden grundigt før De monterer enheden INSTALLATIONSMANUAL Läs bruksa...

Page 2: ...rly installed it may cause water leakage electric shock or fire Do not remodel the unit Consult an installer for repairs If alterations or repairs are not performed correctly it may cause water leakage electric shock or fire The user should never attempt to repair the unit or transfer it to another location If the unit is installed improperly it may cause water leakage electric shock or fire If th...

Page 3: ...unit is not properly grounded there may be a risk to get an electric shock Make sure to use circuit breakers ground fault interrupter isolating switch B fuse and molded case circuit breaker with the specified capacity If the circuit breaker capacity is larger than the specified capacity break down or fire may result 1 4 Before starting the test run Caution Turn on the main power switch more than 1...

Page 4: ... shows three examples of precautions against strong winds 1 Face the air outlet towards the nearest available wall keeping about 50 cm dis tance Fig 2 2 2 Install an optional air guide if the unit is installed in a location where strong winds such as a typhoon etc may directly blow to the air outlet Fig 2 3 A Air outlet guide 3 Position the unit so that the outlet air can blow at right angle to th...

Page 5: ...que at the water piping connection is 50 N m Check if water leaks after installation Use the water pressure in more than 0 MPa gauge and less than 0 3MPa gauge Use the inlet water of higher than 5 C and lower than 55 C 5 2 Water quality condition The water in a system should be clean and with a pH value of 6 5 8 0 The followings are the maximum values Calcium 100mg L Chlorine 100mg L Iron manganes...

Page 6: ...S1 S2 S3 Warning In case of A control wiring there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line Therefore please turn off the main power supply when servicing And do not touch the S1 S2 S3 terminals when the power is energized If isolator should be used between indoor unit and out...

Page 7: ... CNDM connector option on the control board of the outdoor unit The ability varies according to the outdoor temperature and conditions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA Option 2 SW1 ON Low noise mode SW1 OFF Normal operation A Circuit diagram example low noise mode B On site arrangement C External input adapter PAC SC36NA D Outdoor unit control bo...

Page 8: ...act address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...

Reviews: