background image

2

Contents

1. Safety precautions

   Before installing the unit, make sure you read all the “Safety precau-

tions”. 

After installation, perform the test run to ensure normal operation. Then explain 
your customer the “Safety Precautions,” use, and maintenance of the unit based 
on the information in the Operation Manual. Both the Installation Manual and the 
Operation Manual must be given to the user. These manuals must always be kept 
by the actual users.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels attached to the unit.

 Warning:

Precautions that must be observed to prevent injuries or death.

 Caution:

Precautions that must be observed to prevent damages to the unit.

1.  Safety precautions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2
2.  Installation location   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3
3.  Installation procedures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4
4.  Drainage piping work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

5.  Water piping work   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5
6.  Electrical work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5
7.  Test run  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6
8.  Special function  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7

 Warning:

•  

The unit must not be installed by the user. Ask an installer or an autho-
rized technician to install the unit. If the unit is installed improperly, water 
leakage, electric shock, or fi re may be caused.

•  

The unit must be installed according to the instructions in order to mini-
mize the risk of damages by earthquakes, typhoons, or strong winds. Im-
properly installed unit may fall down and cause damages or injuries.

•  

The unit must be securely installed on a structure that can sustain its 
weight. If the unit is mounted on an unstable structure, it may fall down 
and cause damages or injuries.

•  

If the air to water heat pump is installed in an enclosed area, measures 
must be taken to prevent the refrigerant concentration in the room in the 
event of refrigerant leakage. Consult an installer regarding the appropriate 
measures. Should the refrigerant leak and cause the concentration oxygen 
in the room may lack.

•  

Ventilate the room if refrigerant leaks during operation. If refrigerant comes 
into contact with a fl ame, poisonous gases will be released.

•  

All electric work must be performed by a qualifi ed technician according to 
local regulations and the instructions given in this manual. The units must 
be powered by dedicated power lines and the correct voltage and circuit 
breakers must be used. Power lines with insuffi cient capacity or incorrect 
electrical work may result in electric shock or fi re.

•  

Only the specified cables can be used for wiring. Connections must be 
made securely without tension on the terminals. If cables are connected or 
installed improperly, It may result in overheating or fi re.

•  

Terminal block cover panel of the outdoor unit must be fi rmly fi xed. If the 
cover panel is mounted improperly, dust and moisture may enter the unit, 
and it may cause electric shock or fi re.

•  

When installing or moving the air to water heat pump, make sure to use the 
specifi ed refrigerant (R410A) to charge the refrigerant lines. Do not either 
mix it with any other refrigerant or allow air to remain within the pipes. Air 
enclosed in the pipes can cause pressure peaks resulting in a rupture and 
other hazards.

•  

Make sure to use accessories authorized by Mitsubishi Electric and ask  
an installer or an authorized technician to install them. If accessories are 
improperly installed, it may cause water leakage, electric shock, or fi re.

•  

Do not remodel the unit. Consult an installer for repairs. If alterations or 
repairs are not performed correctly, it may cause water leakage, electric 
shock, or fi re.

•  

The user should never attempt to repair the unit or transfer it to another 
location. If the unit is installed improperly, it may cause water leakage, 
electric shock, or fi re. If the air to water heat pump needs to be repaired or 
moved, ask an installer or an authorized technician.

•  

After installation has been completed, make sure that refrigerant does not 
leak. If refrigerant leaks into the room and comes into contact with the 
fl ame of a heater or portable cooking range, poisonous gases will be re-
leased.

•  

Use clean enough water which meets water quality standards. The dete-
rioration of water quality may result in the system breakdown or the water 
leakage.

•  

Never use anything other than water as a medium. It may cause a fi re or an 
explosion.

•  

Do not use heated or cooled water that is produced by the air to water 
heat pump directly for drinking or cooking. There is a risk to damage your 
health. There is also a risk that installing the water heat exchanger may 
corrode if the necessary water quality for the air to water heat pump sys-
tem cannot be maintained. If you wish to use the heated or cooled water 
from the heat pump for these purposes, take measure such as to the sec-
ond heat exchanger within the water piping system.

1.1. Before installation 

 Caution:

•  

Do not use the unit in an unusual environment. If the air to water heat 
pump is installed exposed to steam, volatile oil (including machine oil), 
or sulfuric gas, or exposed to briny air, or covered with snow, the perfor-
mance can be signifi cantly reduced and the internal parts can be damaged.

•  

Do not install the unit where combustible gases may leak, be produced, 
flow, or accumulate. If combustible gas accumulates around the unit, it 
may cause fi re or explosion.

•  

The outdoor unit produces condensate during the heating operation. Make 
sure to provide drainage around the outdoor unit if such condensate is 
likely to cause damage.

•  

When installing the unit in a hospital or in a building where communication 
equipments are installed, you may need to take measures to noise and 
electronic interference. Inverters, home appliances, high-frequency medi-
cal equipment, and radio communications equipment can cause the air to 
water heat pump to malfunction or to breakdown. At the same time, the 
noise and electronic interference from the air to water heat pump unit may 
disturb the proper operation of medical equipment, and communications 
equipment.

1.2. Before installation (relocation) 

 Caution:

•  

Be fully careful when moving the units. The unit must be carried by at least 
2 people, as it weighs 20 kg or more. Do not hold the packaging bands. 
Wear protective gloves to unpack and to move it, in order to avoid your 
hands be injured by fi ns or other parts.

•  

Be sure to safely dispose of the packaging materials. Packaging materials, 
such as nails and other metal or wooden parts may cause injuries.

•  

The base of the outdoor unit must be periodically checked to ensure not 
being loose, cracked or damaged. If such defects are left untreated, the 
unit may fall down and cause damage or injuries.

•  

Do not wash the air to water heat pump unit. You may receive an electric 
shock.

Summary of Contents for PUHZ-W85VHA

Page 1: ...εγκατάστασης της εσωτερικής μονάδας προτού εγκαταστήστε τη μονάδα MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade interior antes de instalar a unidade INSTALLATIONSMANUAL Læs af sikkerhedshensyn denne vejledning samt monteringsvejledningen til indendørsenheden grundigt før De monterer enheden INSTALLATIONSMANUAL Läs bruksa...

Page 2: ...rly installed it may cause water leakage electric shock or fire Do not remodel the unit Consult an installer for repairs If alterations or repairs are not performed correctly it may cause water leakage electric shock or fire The user should never attempt to repair the unit or transfer it to another location If the unit is installed improperly it may cause water leakage electric shock or fire If th...

Page 3: ...unit is not properly grounded there may be a risk to get an electric shock Make sure to use circuit breakers ground fault interrupter isolating switch B fuse and molded case circuit breaker with the specified capacity If the circuit breaker capacity is larger than the specified capacity break down or fire may result 1 4 Before starting the test run Caution Turn on the main power switch more than 1...

Page 4: ... shows three examples of precautions against strong winds 1 Face the air outlet towards the nearest available wall keeping about 50 cm dis tance Fig 2 2 2 Install an optional air guide if the unit is installed in a location where strong winds such as a typhoon etc may directly blow to the air outlet Fig 2 3 A Air outlet guide 3 Position the unit so that the outlet air can blow at right angle to th...

Page 5: ...que at the water piping connection is 50 N m Check if water leaks after installation Use the water pressure in more than 0 MPa gauge and less than 0 3MPa gauge Use the inlet water of higher than 5 C and lower than 55 C 5 2 Water quality condition The water in a system should be clean and with a pH value of 6 5 8 0 The followings are the maximum values Calcium 100mg L Chlorine 100mg L Iron manganes...

Page 6: ...S1 S2 S3 Warning In case of A control wiring there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line Therefore please turn off the main power supply when servicing And do not touch the S1 S2 S3 terminals when the power is energized If isolator should be used between indoor unit and out...

Page 7: ... CNDM connector option on the control board of the outdoor unit The ability varies according to the outdoor temperature and conditions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA Option 2 SW1 ON Low noise mode SW1 OFF Normal operation A Circuit diagram example low noise mode B On site arrangement C External input adapter PAC SC36NA D Outdoor unit control bo...

Page 8: ...act address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...

Reviews: