19
Model name
Indoor unit
PCA-RP71HA
PCA-RP125HA
PCA-RP125HA
Outdoor unit
PUHZ-RP71VHA2
PUHZ-RP125VHA2
PUHZ-RP125YHA2
Cooling
Capacity
Btu/h
24,200
42,700
42,700
kW
7.1(3.3-8.1)
12.5(5.5-14.0)
12.5(5.5-14.0)
Total input
kW
2.21
3.88
3.88
EER
3.21
3.22
3.22
Energy label class
A
A
A
SHF
0.74
0.77
0.77
Heating
Capacity
Btu/h
27,300
47,800
47,800
kW
7.6(3.5-10.2)
13.8(5.0-16.0)
13.8(5.0-16.0)
Total input
kW
2.23
4.05
4.05
COP
3.41
3.41
3.41
Energy label class
B
B
B
Booster heater
kW
-
-
-
Power supply
Phase
[
1
3
Cycle
Hz
50
50
Voltage
V
230
400
Breaker size
A
25
16
Indoor unit
Air flow
CMM
17-19
30-38
(Low-High)
CFM
600-670
1060-1350
External pressure
Pa
0
0
Sound level
dB(A)
34-38
44-50
(Low-High)
External finish
Stainless steel
Dimension
W : mm
1136
1520
D : mm
650
H : mm
280
W : inch
44-3/4
59-7/8
D : inch
25-5/8
H : inch
11
Weight
kg
41
56
lbs
90
124
Unit drain pipe I.D.
mm
26
inch
1
Outdoor unit
Air flow
CMM
55
100
CFM
1,940
3,530
Sound level at cooling
dB(A)
47
50
Sound level at heating
dB(A)
48
52
External finish
Ivory Munsell 3Y 7.8/1.1
Dimension
W : mm
950
950
D : mm
330+30
330+30
H : mm
943
1350
W : inch
37-3/8
37-3/8
D : inch
13 + 1-3/16
13 + 1-3/16
H : inch
37-1/8
53-1/8
Weight
kg
75
116
130
lbs
165
256
287
Refrigerant pipe size
Gas side O.D.
mm
15.88
15.88
inch
5/8
5/8
Liquid side O.D.
mm
9.52
9.52
inch
3/8
3/8
Refrigerant pipe length
Height difference
m
Max. 30
Max. 30
Length
m
Max. 50
Max. 75
NOTE:
1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
:
(80˚F) W.B. 19
:
(66˚F)
Outdoor : D.B. 35
:
(95˚F) W.B. 24
:
(75˚F)
Heating Indoor : D.B. 20
:
(68˚F)
Outdoor : D.B. 7
:
(45˚F)
W.B. 6
:
(43˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
Lower limit D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
1
Heating
Upper limit D.B. 28˚C
D.B. 21˚C, W.B. 15˚C
Lower limit D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
w
2
4. Above data based on indicated voltage
w
1. If optional Air protect guide installed. D.B.-15
:
w
2. For RP125 D.B. -20
:
, W.B. -20
:
Indoor unit
Single phase 230V 50Hz
V: Single phase 230V 50Hz, Y: 3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz (RP125Y : 342~457V, 50Hz)
OCS05A-1.qxp 06.5.15 0:50 PM Page 19
Summary of Contents for PUHZ-RP140VHA2
Page 40: ...40 WIRED REMOTE CONTROLLER Unit mm 130 120 19 ...
Page 41: ...41 WIRELESS REMOTE CONTROLLER Unit mm 159 3 55 58 19 ...
Page 65: ...65 9 2 PLA RP AA 2 9 2 1 FRESH AIR INTAKE AMOUNT ...
Page 66: ...66 ...
Page 67: ...67 9 2 2 BRANCH DUCT Installation at site ...
Page 76: ...76 PEAD RP60GA PEAD RP71GA ...
Page 77: ...77 PEAD RP100GA ...
Page 81: ...81 ...