13
OCH756
4
DATA
4-1. REFILLING REFRIGERANT CHARGE (R32: kg)
4-2. COMPRESSOR TECHNICAL DATA
Service Ref.
PUD-SWM60VAAR1
PUD-SWM80VAAR1
PUD-SWM100VAAR1
PUD-SWM120VAAR1
PUD-SWM80YAAR1
PUD-SWM100YAAR1
PUD-SWM120YAAR1
PUD-SHWM60VAAR1
PUD-SHWM80VAAR1
PUD-SHWM100VAAR1
PUD-SHWM120VAAR1
Compressor model
DVB28FBAMT
DVB28FBBMT
DVK28FBAMT
Winding
Resistance
(Ω)
U-V
0.74
0.94
0.74
U-W
0.74
0.94
0.74
W-V
0.74
0.94
0.74
(Winding temperature at 20°C)
4-3. NOISE CRITERION CURVES
PUD-SWM60VAAR1
PUD-SHWM60VAAR1
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
90
80
70
60
50
40
30
20
10
OCT
AVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
µbar)
63
125
250
500
1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
BAND CENTER FREQUENCIES, Hz
MODE
HEATING
SPL(dB)
41
LINE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
90
80
70
60
50
40
30
20
10
OCT
AVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
µbar)
63
125
250
500
1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
BAND CENTER FREQUENCIES, Hz
MODE
HEATING
SPL(dB)
42
LINE
Service Ref.
PUD-SHWM80YAAR1
PUD-SHWM100YAAR1
PUD-SHWM120YAAR1
PUD-SHWM140VAAR1
PUD-SHWM140YAAR1
Compressor model
DVK28FBBMT
DVK36FBEMT
DVK36FBBMT
Winding
Resistance
(Ω)
U-V
0.94
0.32
0.94
U-W
0.94
0.32
0.94
W-V
0.94
0.32
0.94
PUD-SWM80VAAR1
PUD-SWM80YAAR1
PUD-SHWM80VAAR1
PUD-SHWM80YAAR1
Model
Permitted pipe
length
Initial amount of
refrigerant
Additional refrigerant charging amount
Maximum amount of
refrigerant
Up to 15 m
Exceeding 15 m
SWM60, 80
2 m - 30 m
1.3 kg
20 g × (refrigerant piping length (m) – 15)
1.60 kg
SWM100, 120
2 m - 30 m
1.6 kg
20 g × (refrigerant piping length (m) – 15)
1.83 kg
SHWM60, 80
2 m - 30 m
1.4 kg
20 g × (refrigerant piping length (m) – 15)
1.70 kg
SHWM100, 120
2 m - 30 m
1.7 kg
20 g × (refrigerant piping length (m) – 15)
1.83 kg
SHWM140
2 m - 25 m
1.7 kg
20 g × (refrigerant piping length (m) – 15)
1.83 kg