12
PFD-P500VM-E
Unit : mm
50
100
140
50
50
390
100
68
124
135
Note
1.
Be sure to set up a trap for Emergency
drain piping.
(Trap height:beyond 100mm)
(Trap is not necessary for main drain piping.)
2.
Approve this figure because it is refused
for the improvement and specification
subject to change without notice.
3.
Amputate a gas pipe/liquid pipe in the
fixed height at the time of 2 refrigerant
circuit connection, and connect it with
the local pipe.
Refrig. piping <liquid> in 2 refrig. circuit system
ø
9.52 braze No.1
Refrig. piping <gas> in 2 refrig. circuit system
type P450:
ø
19.05 braze, type P560:
ø
22.2 braze No.1
Refrig. piping <liquid>
ø
15.88 braze
Refrig. piping <gas>
ø
28.58 braze
Hole for No.2 gas pipe
connecting(
ø
42) in 2
refrig. circuit system
Hole for No.2 liquid pipe
connecting(
ø
24) in 2
refrig. circuit system
Hole for liquid pipe connecting(
ø
34)
Hole for No.1 liquid pipe connecting
(ø
24) in 2 refrig. circuit system
Bolt holes:8-
ø
18
Hole for No.1 gas pipe connecting(
ø
42)
in 2 refrig. circuit system
Hole for gas pipe connecting(
ø
48)
Main drain piping connecting<Rp1-1/4>
Drain piping connection
for humidifier
<Accessory>
· Lifting bolts
······
4pc.
· Front panel opening and closing key
······
1pc.
Air inlet
Service space
Indoor unit
Pipe execution
space
Panel opening
and closing
dimension
Indoor unit
Unit surface
figure
Service space
400 or more
Unit front
figure
1000 or more
✻
1
200 or more
✻
1.
It is necessary for the removal
of the panel beyond 600mm.
500 or more
710
Refrig. piping <gas> in 2 refrig. circuit system
type P450:
ø
19.05 braze,
type P560:
ø
22.2 braze No.2
680
<2-
ø
32 knook out
hole>
<
ø
32 knook out hole>
Air outlet
Air inlet
Power supply
:White
Operating
:Green
Check
:Yellow
Failure1
:Red
Failure2
:Red
<Normal/Local>
(Accessory)
<view from A>
<Rp1-1/4>
Air
outlet
Hole for liquid side pipe connecting
or No.1 gas side pipe connecting(
ø
42)
in 2 refrig. circuit system
Hole for No.2 gas side pipe connecting(
ø
42)
in 2 refrig. circuit system
100
100
1780
1940
100
20
20
20
65
321
100
410
359
241
740
359
580
305
320
220
370
20
Emergency drain piping connection <Rp1-1/4>
Hole for No.1 liquid side pipe connecting
(ø
24) in 2 refrig. circuit system
Hole for the power supply(
ø
60)
1950
780
Hole for gas side pipe connecting or
No.2 liquid side pipe connecting(
ø
48)
in 2 refrig. circuit system
440
Air
outlet
185
379
135
Refrig. piping <liquid> in 2 refrig. circuit
system
ø
9.52 braze No.2
68
120
Hole for the control wiring <
ø
32 knook out hole>
Hole for the power supply <
ø
32 knook out hole>
220
150
81
Hole for the control wiring(
ø
60)
Panel
68
Lifting bolts
171
A
Control box
Lamp
Filter
Remote controller
838
Hole for the control wiring
1980
124
68
Hole for the power
supply(Body)
Changeover switch