Appendix C : System Objects
There are 5 ‘System’ objects contained within the Procon BAC-IP/50. A
description of each is detailed below.
System Object
Description
Mnet Comms State
Provides an indication of the communication status
between the G-50 and the Mitsubishi M-Net network.
Inactive : M-Net Initialising
Active : M-Net OK
Note: While M-Net is initialising, the air-conditioning is
effectively offline to control and monitoring
requests.
System Forced Off (Setup)
Writeable object to enable and disable the global on/off
command.
System Forced Off (State)
Readable object giving indication of the global on/off
command.
G50 Comms State
Provides an indication of the communication status
between the Procon BAC-IP/50 and the G-50.
Inactive : G-50 not responding
Active : G-50 comms OK
Note: ‘G-50 not responding’ either means the G-50 is
switched off or is not connected to the network.
New_Setting_Compare
Selects the way in which the Procon BAC-IP/50 handles
new command settings.
Inactive : New command values are written
regardless of the current setting.
Active : New command values are only written if the new
setting is different to the current setting.
(Useful for systems which continuously write to
the command parameters).