13
Appendix B : Reset Button
The Reset button has 2 functions :
1) To restore various internal settings to their factory defaults,
2) To force the unit into ‘bootloader’ mode ready for a firmware
update.
Function 1 – Restore Factory Defaults
There are 2 levels to this function.
Level 1 : With the unit already ON, press and hold in the reset
button. After approximately 5 seconds the ‘Device Reset’
light will start to flash slowly. Releasing the reset button
while the light is flashing slowly will activate Level 1, and
then reset the unit.
Settings Restored:
Configuration via network
Enabled
Level 2 : With the unit already ON, press and hold in the reset
button. After approximately 5 seconds the ‘Device Reset’
light will start to flash slowly. Continue to hold in the reset
button until the light starts to flash rapidly. Releasing the
reset button while the light is flashing rapidly will activate
Level 2, and then reset the unit.
Settings Restored:
IP Address
192.168.1.10
Gateway
Address
192.168.1.10
Subnet
Mask
255.255.255.0
G50 IP Address
192.168.1.1
BACnet Device ID
10
BACnet
Device
Name
Procon
BAC-IP/50
Foreign Device Reg TTL
1800