GB
Please observe the following precautions during installation.
I
P
portant notes on
Z
ater pipe
Z
or
N
installation
The water pressure resistance of the water pipes in the heat source unit is 1. MPa
[145psi].
Please connect the water pipework of each indoor unit to the connect port on the
HBC. Failure to do so will result in incorrect running.
Please list the indoor units on the naming plate in the HBC unit with addresses and
end connection numbers.
If the number of indoor units are less than the number of ports on the HBC, the
unused ports can be capped. Without a cap, water will leak.
Use the reverse-return method to insure proper pipe resistance to each unit.
Provide some oints and bulbs around inlet outlet of each unit for easy maintenance,
checkup, and replacement.
Install a suitable air vent on the water pipe. After owing water through the pipe,
vent any excess air.
Secure the pipes with metal tting, positioning them in locations to protect pipes
against breakage and bending.
Do not confuse the water intake and outlet piping. Error code 51 2 will appear on
the remote controller if a test run is performed with the pipe-work installed incorrectly
(inlet connected to outlet and vice versa).
This unit doesn’t include a heater to prevent freezing within tubes. If the water ow
is stopped on low ambient, drain the water out.
The unused knockout holes should be closed and the refrigerant pipes, water pipes,
power source and transmission wires access holes should be lled with putty.
Install water pipe so that the water ow rate will be maintained.
Wrap sealing tape as follows.
1
Wrap the oint with sealing tape following the direction of the threads (clockwise),
do not wrap the tape over the edge.
2
Overlap the sealing tape by two-thirds to three-fourths of its width on each turn.
Press the tape with your ngers so that it is tight against each thread.
3
Do not wrap the 1.5th through 2nd farthest threads away from the pipe end.
Connecting
Z
ater pipes
Hold the pipe on the unit side in place with a spanner when installing the pipes or
strainer. Tighten screws to a torque of 4 N m.
If there is a risk of freezing, carry out a procedure to prevent it.
When connecting heat source unit water piping and on site water piping, apply liquid
sealing material for water piping over the sealing tape before connection.
Do not use steel pipes as water pipes.
- Copper pipes are recommended.
Install a strainer (4 mesh or more) on the pipe next to the valve to remove the
foreign matters.
Be sure to provide anti-dew condensation treatment on the inlet and outlet of the
water pipes and on the valve. Provide an appropriate treatment on the end surface
of the dew proo ng material to keep condensation out.
When water has been supplied to the water pipework, purge the system of air.
The details of air purging can be found separately in the water circuit maintenance
manual.
2
Water pipe insulation
1. Connect the water pipes of each indoor unit to the same (correct) end connection
numbers as indicated on the indoor unit connection section of each HBC controller.
If connected to wrong end connection numbers, there will be no normal operation.
2. List indoor unit model names in the name plate on the HBC controller control box
(for identi cation purposes), and HBC controller end connection numbers and ad-
dress numbers in the name plate on the indoor unit side.
Seal unused end connections using cover caps (sold separately). Not replacing on
end cap will lead to water leakage.
3. Be sure to add insulation work to water piping by covering water pipework separately
with enough thickness heat-resistant polyethylene, so that no gap is observed in
the oint between indoor unit and insulating material, and insulating materials them-
selves. When insulation work is insuf cient, there is a possibility of condensation,
etc. Pay special attention to insulation work in the ceiling plenum.
[Fig.4-1]
Insulation materials for the pipes to be added on site must meet the following
speci cations:
HBC controller
-indoor unit
2 mm or more
This speci cation is based on copper for water piping. When using plastic pipework,
choose a thickness based on the plastic pipe performance.
Installation of pipes in a high-temperature high-humidity environment, such as the
top oor of a building, may require the use of insulation materials thicker than the
ones speci ed in the chart above.
When certain speci cations presented by the client must be met, ensure that they
also meet the speci cations on the chart above.
4. Leakproof the water pipework, valves and drain pipework. Leakproof all the way to,
and include pipe ends so that condensation cannot enter the insulated pipework.
5. Apply caulking around the ends of the insulation to prevent condensation getting
between the pipework and insulation.
6 Add a drain valve so that the unit and pipework can be drained.
7. Ensure there are no gaps in the pipework insulation. Insulate the pipework right up
to the unit.
. Ensure that the gradient of the drain pan pipework is such that discharge can only
blow out.
A
Locally procured insulating material for pipes
B
Bind here using band or tape.
C
Do not leave any opening.
D
Lap margin: more than 4 mm
E
Insulating material ( eld supply)
F
Unit side insulating material
F
E
D
C
B
A
B
A
Fig
-
Fig
-2
A
Water pipe: To HBC unit
B
Water pipe: From HBC unit