18
Fig.1
Fig.2
Fig.3
Fig.4
8-2. FAN and FAN MOTOR
OPERATING PROCEDURE
PHOTOS
Models 15~54
1.Removing the control box.
(1) Remove the control box cover and terminal bed cover with
procedure 8-1.
(2) Remove the fan motor connectors.
(3) Remove the fixing screws (two) of the control box and slide
the control box to remove.(Fig. 1)
(4) Move the control box to place that is not block operation.
(Fig. 2)
2.Removing the fan motor
Models 15~30
*After motor base (D) and bell mouse (C) attached the fan
case (B) removed,motor (A) can be pull with motor base
and fan along rail.
(1) Remove the fan motor connector (E).
(2) Loosen the fixing screws (F) (three) of the bell mouse (C),
and removed the bell mouse (D) turning screws in direction
arrow (counterclockwise).(Fig. 3)
(3) Remove the fixing screws (four) of the motor base(D).
Notice: It's necessary using the driver over 30cm length to
remove the fixing screws (a) .
(Fixing screws are placed back)
Be careful on removing heavy parts.
Fixing screws
Motor base (D)
Fixing screws (a)
Control box
Control box
(A)
(E)
(B)
(C)
(D)
Fixing screws (F)
Loosen fixing screws (not remove)
Models 40~63