7. Electrical work
Mode no.
Setting no. Initial setting
Setting
01
1
*2
2
*2
1
䡬
02
2
3
1
䡬
03
2
3
04
1
2
䡬
05
1
䡬
2
Function table
Select unit number 00
Mode
Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Auto mode
Settings
Not available
Available
*1
Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
240 V
220 V, 230 V
Energy saving cycle automatically enabled
Energy saving cycle automatically disabled
Mode
Filter sign
Fan speed
No. of air outlets
Installed options (high-performance filter)
Up/down vane setting
Energy saving air flow
(Heating mode)
Settings
100Hr
2500Hr
No filter sign indicator
Standard (PLH/PLA-P·AA(H)/PLA-RP·AA)/Silent (PLH/PLA-P·KA(H),
PCH/PCA)
High ceiling
1
(PLH/PLA-P·AA(H)/PLA-RP·AA)/Standard (PLH/PLA-
P·KA(H), PCH/PCA)
High ceiling
2
(PLH/PLA-P·AA(H)/PLA-RP·AA)/High ceiling (PLH/
PLA-P·KA(H), PCH/PCA)
4 directions
3 directions
2 directions
Not supported
Supported
No vanes
Equipped with vanes (vanes angle setup
1
)
Equipped with vanes (vanes angle setup
2
)
Disabled
Enabled
Mode no.
Setting no. Initial setting
Setting
1
07
2
3
䡬
1
08
2
–
3
1
09
2
–
3
10
1
–
2
11
1
2
–
3
12
1
–
2
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
1
2
3
4
7.3. Function settings
7.3.1. For wired remote controller (Fig. 7-5)
⁄
Mode number
⁄
Setting number
⁄
Refrigerant address
⁄
Unit number
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.
1
Go to the function setting mode.
Switch OFF the remote controller.
Press the
A
and
B
buttons simultaneously and hold them for at least 2 seconds. FUNCTION will start to flash.
2
Use the
C
button to set the refrigerant address (
3
) to 00.
3
Press
D
and [--] will start to flash in the unit number (
4
) display.
4
Use the
C
button to set the unit number (
4
) to 00.
5
Press the
E
MODE button to designate the refrigerant address/unit number. [--] will flash in the mode number (
1
) display momentarily.
6
Press the
F
buttons to set the mode number (
1
) to 04.
7
Press the
G
button and the current set setting number (
2
) will flash.
Use the
F
button to switch the setting number to the power supply voltage to be used.
Power supply voltage
240 V
: setting number = 1
220 V, 230 V : setting number = 2
8
Press the MODE button
E
and the setting number (
1
) and (
2
) will change to being on constantly and the contents of the setting can be confirmed.
9
Press the FILTER
A
and TEST RUN
B
buttons simultaneously for at least two seconds. The function selection screen will disappear momentarily and the air conditioner
OFF display will appear.
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.