48
7. Main remote controller operation
Engineers Forms
Commissioning/Field settings record sheet (continued from the previous page)
Main remote controller screen
Parameters
Default
setting
Field
setting Notes
Service menu
Pump speed
Pump speed (1 - 5)
5
Heat source setting
Standard/Heater/Boiler/Hybrid *7
Standard
Operation
settings
Heating operation
*8
Flow temp.range
*10
Min.temp. (25 - 45°C)
30°C
Max.temp. (35 - 60°C)
50°C
Room temp.control
*13
Mode (Normal/Fast)
Normal
Interval (10 - 60min)
10min
Heat pump thermo
diff.adjust
On/Off *6
On
Lower limit (-9 - −1°C)
−5°C
Upper limit (+3 - +5°C)
5°C
Freeze stat function *11
Outdoor ambient temp. (3 - 20°C) / **
5°C
Simultaneous operation (DHW/Heating)
On/Off *6
Off
Outdoor ambient temp. (−30 - +10°C) *4
−15°C
Cold weather function
On/Off *6
Off
Outdoor ambient temp. (−30 - −10°C) *4
−15°C
Boiler operation
Hybrid settings Outdoor ambient temp.
(−30 - +10°C) *4
−15°C
Priority mode
(Ambient/Cost/CO
2)
Ambient
Intelligent set-
tings
Energy
price
*9
Electricity
(0.001 - 999 */kWh)
0.5 */kWh
Boiler
(0.001 - 999 */kWh)
0.5 */kWh
CO
2
emis-
sion
Electricity
(0.001 - 999 kg
-CO2/kWh)
0.5 kg -CO2/kWh
Boiler
(0.001 - 999 kg
-CO2/kWh)
0.5 kg -CO2/kWh
Heat
source
Heat pump ca-
pacity
(1 - 40 kW)
11.2 kW
Boiler efficiency
(25 - 150%)
80%
Booster heater 1
capacity
(0 - 30 kW)
2 kW
Booster heater 2
capacity
(0 - 30 kW)
4 kW
Floor dry up function
On/Off *6
Off
Target temp.
Start&Finish (25 - 60°C)
30°C
Max. temp. (25 - 60°C)
45°C
Max. temp. period (1 - 20 days) 5 days
Flow temp.
(Increase)
Temp. increase step (+1 - +10°C) +5°C
Increase interval (1 - 7 days) 2 days
Flow temp.
(Decrease)
Temp. decrease step (−1 - −
10°C)
−
5°C
Decrease interval (1 - 7 days) 2 days
Energy
monitor
settings
Electric heater
capacity
Booster heater 1
capacity
0 - 30kW
2kW
Booster heater 2
capacity
0 - 30kW
4kW
Immersion heater
capacity
0 - 30kW
0kW
Delivered energy adjustment
−50 - +50%
0%
Water pump input
Pump 1
0 - 200W or ***(factory fitted pump)
***
Pump 2
0 - 200W
0W
Pump 3
0 - 200W
0W
Electric energy meter
0.1/1/10/100/1000 pulse/kWh
1 pulse/kWh
Heat meter
0.1/1/10/100/1000 pulse/kWh
1 pulse/kWh
External in-
put settings
Demand control (IN4)
Heat source OFF/Boiler operation
Boiler
operation
Outdoor thermostat (IN5)
Heater operation/Boiler operation
Boiler
operation
*6 On: the function is active; Off: the function is inactive.
*7 When DIP SW1-1 is set to OFF “WITHOUT Boiler” or SW2-6 is set to OFF “WITHOUT Mixing tank”, neither Boiler nor Hybrid can be selected.
*8 Valid only when operating in Room temp. control mode.
*9 “*” of “*/kWh” represents currency unit (e.g. € or £ or the like)
*10 Valid only when operating in Heating room temperature.
*11 If asterisk (**) is chosen freeze stat function is deactivated. (i.e. primary water freeze risk)
*12 Only available if DHW tank present in system.
*13 When DIP SW5-2 is set to OFF, this function is active.
Summary of Contents for PAC-SIF051B-E
Page 69: ......