EN-9
3. System
L
N
TB6
FTC2BR
To control
board
Wiring
circuit
breaker
or
Isolating
switch
L
Outdoor unit
S2
S3
S1
S2
S3
S1
N
Wiring
circuit
breaker
or
Isolating
switch
Earth
leakage
circuit
breaker
Power
supply
~/N
230V
50Hz
Power
supply
~/N
230V
50Hz
Earth
leakage
circuit
breaker
*1.
N
L2
L3
L
N
TB6
FTC2BR
To control
board
Wiring
circuit
breaker
or
Isolating
switch
Power
supply
~/N
230V
50Hz
Outdoor unit
S2
S3
S1
S2
S3
S1
Wiring
circuit
breaker
or
Isolating
switch
Earth
leakage
circuit
breaker
Power
supply
3N~
400V
50Hz
Earth
leakage
circuit
breaker
*1
L1
INPUT
Remote controller
Thermistor
OUTPUT
Power cables
CN401
(WH)
CN1A
(WH)
CNS2
(RD)
To outdoor unit
Option 2: FTC2BR powered by independent source
<Fig. 4.1.4>
Electrical connections 1 phase/3 phase
<Fig. 4.1.3>
Wiring for FTC2BR
<1 phase>
<3 phase>
FTC2BR power supply
~/N 230 V 50 Hz
FTC2BR input capacity
16A
Wiring
Wiring No. × size(mm²)
FTC2BR - power supply
2×Min. 1.5
FTC2BR - power supply earth
1×Min. 1.5
FTC2BR - Outdoor unit *2
2×Min. 0.3
FTC2BR - Outdoor unit earth
Circuit rating
FTC2BR L-N *3
230V AC
FTC2BR - Outdoor unit S1 - S2 *3
FTC2BR - Outdoor unit S2 - S3 *3
24V DC
If FTC2BR and outdoor units have separate power supplies, the following
requirements MUST carried out.
• Remove the short circuited connector CNS2.
• Turn on the outdoor unit before the FTC2BR.
• Outdoor unit DIP switch settings changed to SW8-3 ON.
• Power by independent source is not available for particular models of outdoor unit
model.
For more detail, refer to the connecting outdoor unit installation manual.
Notes:
1. Do not run the low voltage cables through a slot that the high voltage ca-
bles go through.
2. Do not bundle power cables together with other cables.
3. Bundle cables as Fig. 4.1.3 by using clamps.
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided.
Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase
conductors of the supply.
*2. Max. 45 m
If 2.5 mm² used, Max. 50 m
If 2.5 mm² used and S3 separated, Max. 80 m
*3. The values given in the table above are not always measured against the ground
value.
Notes:
1. Wiring size must comply with the applicable local and national codes.
2. FTC2BR/outdoor unit connecting cords shall not be lighter than
polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
FTC2BR unit power supply cords shall not be lighter than
polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
en