4. Electrical work
• Remote switch Type A (4 bit - 8 setting)/Type B (1 bit - 1 setting)
Demand control is available by connecting remote switches with terminal No.10 - 14.
Make sure to use the non-voltage switch (for the remote switch)
Remote switch cable length : Maximum 10m
Remote switch : Minimum applicable load 12V DC, 1mA
• 4-20mA / 1-5V / 0-10V / 0-10kΩ
1
Use 4-20mA / 1-5V / 0-10V
Connect the transmission cables to No. 11 and 12 on the terminal block (TB61).
No. 11 on the terminal block(TB62) : Plus side
No. 12 on the terminal block(TB62) : Minus side (Reference side)
2
Use variable resistor (0-10kΩ)
Connect the transmission cables to No. 9 and 10 on the terminal block (TB61).
Note:
The values of the "capacity setting" table on the previous page show the center
of the input value.
Cable length: Maximum 10m
<Photo 4.1.4>
• External function setting
This function is setting operation mode or stopping compressor, by the external signal.
TB62
Item
OFF
ON
Remark
1-2 (IN1)
Forced Comp. OFF *1 Normal
Forced Comp. OFF
3-4 (IN2)Item
Fixed operation mode Cooling
Heating
Available when SW2-1 and SW2-2 are ON
*1 The operation continues during defrosting operation.
The “Forced Comp. OFF” signal should not be turned ON frequently. It should only
be used if an abnormality occurs.
Cable length : Maximum 10m
Remote switch : Minimum applicable load 12V DC, 1mA
4.1.5. Connecting External Output
Name
Terminal block Item
OFF
ON
OUT1
TB141 5-6
Operation Output
OFF
ON
OUT2
TB141 3-4
Error Output
Normal
Error
OUT3
TB141 1-2
Comp. ON Output
OFF(Comp. OFF) ON(Comp. ON)
OUT4
TB142 5-6
Defrost Output
OFF
ON(Defrosting)
OUT5
TB142 3-4
Mode(Cool) Output
OFF
ON(Cooling)
OUT6
TB142 1-2
Mode(Heat) Output
OFF
ON(Heating)
OUT7
TB143 5-6
Self protection Output OFF
ON
OUT8
TB143 3-4
Pre-Defrost Output
*1
OFF
ON
*1 The output may not be available depending on connected outdoor unit models.
Cable length : Maximum 50m
Output specification : Non-voltage switch 1A, 240V AC/30V DC or less
10 mA, 5 V DC or more
*Connect the surge absorber according to the load at site.
<Photo 4.1.5>
TB143
OUT6
TB143
1
OUT8 OUT7
2 3 4 5 6
TB142
1
OUT5 OUT4
2 3 4 5 6
OUT3
TB141
1
OUT2 OUT1
2 3 4 5 6
X8
X7
X6
X5
X4
X3
X2
X1
TB142
TB141
Note:
• External output signals are separated by basic insulation from other circuit
of interface.
• When intelligent multiple outdoor unit control function is selected, OUT2, OUT3,
OUT4, OUT7 and OUT8 will work individually on each interface.
Caution: When 2 or more external outputs are used, the power supply on
the output side should be the same.
Note:
When using IN1 with intelligent multiple outdoor unit control function, input
IN1 to the interface unit respectively. Input IN2 to the main interface which con
-
nects to the ref. address 0 outdoor unit.
Caution:
The external input signals are separated by basic insulation from power sup
-
ply for the unit.
The external input signals should be separated by supplementary insulation
from where user may touch in case that it is installed where user may touch.
Connect the terminals by using the ring terminals and also insulate the ca
-
bles of adjoining terminals when wiring to terminal block.
TB61
TB62
At site
0-10 kΩ
4-20mA/1-5V/0-10V
Wired remote controller
(For maintenance)
I/F
9
EN
Note:
When using intelligent multiple outdoor unit control function, input the capacity request
signal to the main interface which connects to the ref. address 0 outdoor unit.