• This interface is to connect Mr. Slim inverter outdoor unit of MITSUBISHI ELECTRIC to local applications. Please check the following when designing the local system.
• MITSUBISHI ELECTRIC does not take any responsibility on the local system design. Therefore, MITSUBISHI ELECTRIC does NOT take any responsibility on the failure 

(including outdoor unit) caused by local AHU and system design.

• Conformity of regulations and laws must be confirmed on the system on your side.

7.1. Air flow volume

Standard air flow volume

Model capacity of outdoor unit

ZRP

35

50

60

71

100

125

140

200

250

P

200

250

SHW

80

112

140

230

Maximum air volume

[m³/min]

12.3

18

21

24

33.6

42

48

67.2

81

[m³/h]

738

1080

1260

1440

2016

2520

2880

4032

4860

Minimum air volume

[m³/min]

6.2 

8.6 

10.5 

12.2 

16.3 

21.5 

23.0 

32.6 

37.8 

[m³/h]

372 

516 

630 

732 

978 

1290 

1380 

1956 

2268 

Make sure to keep the air flow volume within the limits of maximum and minimum below.

(1) Maximum air volume

Step mode

Number of 

outdoor unit

Capacities of the

connected outdoor units

Maximum air volume

Manual

2-6

The same

500% of selected outdoor unit's maximum standard air volume 

*1

Different

If smaller capacity outdoor unit's rated heating capacity is under 20% of total 
heating capacity, 500% of bigger capacity outdoor unit's maximum standard air 
volume is allowable.
If smaller capacity outdoor unit's rated heating capacity is 20% or more of total 
heating capacity, 500% of smaller capacity outdoor unit's maximum standard air 
volume is allowable.

1

200% of selected outdoor unit's maximum standard air volume

Auto

2-5

500% of the smallest capacity outdoor unit's maximum standard air volume

1

200% of selected outdoor unit's maximum standard air volume

*1. 600% of selected outdoor unit's maximum standard air volume is available ONLY when 6 same capacity outdoor units are connected.

Note:

• 

When multiple outdoor units are connected, basically select one interlaced heat exchanger which has multiple refrigerant circuit or multiple heat exchanger placed 

in parallel to the air flow. If multiple heat exchangers placed in series with the air flow have to be used, maximum 2 heat exchanger in series are acceptable.

(2) Minimum air volume

Total amount of selected outdoor unit's minimum standard air volume is allowable.

7.2. Indoor heat exchanger 

(1) Indoor heat exchanger volume

Make sure to keep the HEX capacity within the following range.

If the piping length is 30m or shorter, HEX capacity can be increased as follows.

Model capacity of outdoor unit

ZRP

35

50

60

71

100

125

140

200

250

P

200

250

SHW

80

112

140

230

Max. volume  [cm

3

]

Pipe length

30m - 

1050

1500

1800

2130

3000

3750

4200

6000

7500

20m

1350

1800

2700

3030

3900

4650

5100

7800

9300

10m

1650

2100

3600

3930

4800

5550

6000

9600

11100

Min. volume  [cm

3

]

350

500

600

710

1000

1250

1400

2000

2500

Note: Calculate them by linear interpolation in case of other piping lengths not shown on this table. 

(2) Diameter of header

With a bigger size header , the refrigerant flow velocity decreases and this disturbs the sufficient circulation of refrigerant oil. As a result, the refrigerant oil does not 
flow properly and could cause a serious damege of compressor.

Use the pipe whose outside diameter is less than the value shown in the table below.

Model capacity of outdoor unit

ZRP

35

50

60

71

100

125

140

200

250

P

200

250

SHW

80

112

140

230

Max. diameter of header [mm]

{

19

{

28

(3) Withstanding pressure

Design pressure of outdoor unit is 4.15 MPa. Following must be satisfied for burst pressure of connecting application. 

Burst pressure : More than 12.45 MPa (3 times more than design pressure)

(4) Contamination maintenance

1. Wash the inside of heat exchanger to keep it clean. Be sure to rinse not to leave flux. Do not use chlorine detergent when washing.

2. Be sure that the amount of contamination per unit cubic content of heat transfer pipe is less than the following amount.

Example) In case of ø9.52mm

Residual water : 0.6 mg/m, Residual oil : 0.5 mg/m, Solid foreign object : 1.8 mg/m

7.  Requirement on local design

21

EN

Summary of Contents for PAC-IF013B-E

Page 1: ...gen Verwendung vor dem Betrieb der Schnittstelleneinheit das vorliegende Bedienungshandbuch gründlich durchlesen MANUEL D UTILISATION Avant d installer l unité d interface lire attentivement ce guide d utilisation pour une utilisation sûre et correcte BEDIENINGSHANDLEIDING Lees deze bedieningshandleiding voor een veilig en juist gebruik goed door voordat u het interface apparaat bedient MANUAL DE ...

Page 2: ...unted improperly dust and moisture may enter the unit and it may cause electric shock or fire Make sure to use accessories authorised by Mitsubishi Electric and ask an installer or an authorised technician to install them If accessories are improperly installed it may cause electric shock or fire Do not remodel the unit Consult an installer for repairs If alterations or repairs are not performed c...

Page 3: ... kg ACCESSORIES 0 8 kg 2 5 kg ACCESSORIES 0 4 kg Allowable ambient temperature 0 to 35 C 0 to 35 C Allowable ambient humidity 80 RH or less 80 RH or less 2 2 Choosing the interface unit installation location Do not install the interface unit in outdoor location as it is designed for indoor installation only The interface board and casing are not waterproof Avoid locations where the unit is exposed...

Page 4: ...l on temp thermistor TH11 8 Air Handling Unit AHU Local supply 9 AHU local controller Local supply 10 Heat exchanger of AHU Local supply 11 Target air temp thermistor Local supply 12 Louver Local supply 13 Air filter Local supply 14 Heat recovery Local supply 15 Fan Local supply 2 Set the DIP SW 2 8 to ON 3 If outdoor unit is SHW series It s not needed to install this thermistor and set the DIP SW...

Page 5: ... Fig 3 1 3 No Part name System 1 3 1 Interface unit 2 Remote controller 3 Outdoor unit 4 Target air temp thermistor TH1 5 Ref liquid temp thermistor TH2 6 2 Phase temp thermistor TH5 8 7 HEX inlet Coil on temp thermistor TH11 8 Air Handling Unit AHU Local supply 9 AHU local controller Local supply 10 Heat exchanger of AHU Local supply 11 Target air temp thermistor Local supply 12 Louver Local supp...

Page 6: ...in MAX 500m When using this function set the DIP SW 1 8 of all inter face unit to ON Do NOT select STEP 0 for 3 minutes after compressor is ON Keep compressor ON for 3 minutes at least When changing STEP make it less than 5 steps in a single operation and keep at least 5 minutes interval between the changes Keep operation range shown at the following section 3 3 Do NOT send STEP 0 during defrost o...

Page 7: ...gulations the circuit breaker isolating switch located on the outdoor unit should be installed with lockable devices health and safety 3 Max 45 m If 2 5 mm used Max 50 m If 2 5 mm used and S3 separated Max 80 m 4 The values given in the left table are not always measured against the ground value INPUT Remote controller thermistor OUTPUT Power cables 4 1 2 Separate interface unit outdoor unit power...

Page 8: ...Interface unit Outdoor unit 3 2 Min 0 3 Interface unit Outdoor unit earth Circuit rating Interface unit L N 4 230 V AC Interface unit Outdoor unit S1 S2 4 Interface unit Outdoor unit S2 S3 4 24 V DC 2 A breaker with at least 3 0 mm contact separation in each pole shall be provided Use earth leakage breaker NV The breaker shall be provided to ensure disconnection of all active phase conductors of t...

Page 9: ...rosting OUT5 TB142 3 4 Mode Cool Output OFF ON Cooling OUT6 TB142 1 2 Mode Heat Output OFF ON Heating OUT7 TB143 5 6 Self protection Output OFF ON OUT8 TB143 3 4 Pre Defrost Output 1 OFF ON 1 The output may not be available depending on connected outdoor unit models Cable length Maximum 50m Output specification Non voltage switch 1A 240V AC 30V DC or less 10 mA 5 V DC or more Connect the surge abs...

Page 10: ...3 C SW3 4 3 5 Thermo OFF point by HEX inlet air temp difference between target temp and HEX inlet temp For Auto step mode and supply air temp control Compressor is forced to stop when HEX inlet temp is close to target temp to reduce frequent ON OFF cycling under low heating cooling load condition 1 This function is valid only with remote controller 2 This SW must be set to OFF DIP switch Function ...

Page 11: ...on wait until the LED lamps on the interface control board are all off 6 The read and write operations have been verified using the following SD memory cards however these operations are not always guaranteed as the specifica tions of these SD memory cards could change Manufacturer Model Tested in Verbatim 44015 0912 61 Mar 2012 SanDisk SDSDB 002G B35 Oct 2011 Panasonic RP SDP04GE1K Oct 2011 Arvat...

Page 12: ...mote controller either directly on the wall or in the switch box 2 Prepare the following items in the field Double switch box Thin metal conduit Locknut and bushing Cable cover Wall plug 2 Drill an installation hole in the wall Installation using a switch box Drill a hole in the wall for the switch box and install the switch box in the hole Fit the conduit tube into the switch box Direct wall inst...

Page 13: ... deformation or cracks to the remote controller do not overtighten the screws and make an additional installation hole s 6 Cut out the cable access hole Direct wall installation Cut out the knockout hole indicated with grey in Fig 4 3 7 in the front cover by knife or nipper Thread the remote controller cable from the slot behind the bottom case through this access hole 7 Plug the lead wire cable i...

Page 14: ...he remote controller cable along the wall surface Thread the remote controller cable through the cable access hole at the top of the remote controller Seal the gap between the cable and the access hole with putty Use a cable cover Disassembling the top case and the front cover 1 Remove the front cover Insert a flat head screwdriver into either of two open slots at the bottom of the remote controll...

Page 15: ...r mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction con cerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the ap pliance If the refrigeration gas blows out or leaks stop the operation of the air conditioner thoroughly ventilate the room and contact you...

Page 16: ...hile the unit is in operation It blinks while the remote controller is starting up or when there is an error Press to save the setting Main display Press to change the operation mode Main menu Press to move the cursor down Press to return to the previous screen Main display Press to decrease temperature Main menu Press to move the cursor up Press to bring up the Main menu Main display Press to inc...

Page 17: ...e controller related items as necessary Press the SELECT button to save the changes 1 Clock display 2 Temperature unit setting 3 Room temperature display 4 Auto mode Auto cooling heating operation display setting The factory setting is Yes Yes AUTO COOL or AUTO HEAT is displayed during Auto mode Auto cooling heating operation No Only AUTO is displayed during Auto mode Auto cooling heating operatio...

Page 18: ...ure Pressing once changes the value by 1ºC 1ºF Press button 1 ON OFF Press button 7 F1 to display the operation mode Auto 1 2 F1 When the room temperature is higher than the preset temperature cooling operation starts When the room temperature is lower than the preset temperature heating operation starts The current operation mode Auto cool or Auto heat will be displayed after the mode is determin...

Page 19: ... schedule function is NOT available Filter information Maintenance In Service menu Drain pump test run Check functions are NOT available except for Request code in Check function On Off timer Operation On Off times can be set in 5 minute increments Auto Off timer Auto Off time can be set to a value from 30 to 240 in 10 minute increments The initial administrator password is 9999 Change the default...

Page 20: ... DIP SW setting error Intelligent multiple outdoor unit controll Set DIP SW 1 8 to OFF if system is single outdoor unit control Connect between interface units and set Ref address of each outdoor unit See 3 System System error 2 Controller board is incompatible with this model Install interface controller board that is compatible with PAC IF013B E or PAC SIF013B E System error 3 Incompatible contr...

Page 21: ...aced heat exchanger which has multiple refrigerant circuit or multiple heat exchanger placed in parallel to the air flow If multiple heat exchangers placed in series with the air flow have to be used maximum 2 heat exchanger in series are acceptable 2 Minimum air volume Total amount of selected outdoor unit s minimum standard air volume is allowable 7 2 Indoor heat exchanger 1 Indoor heat exchange...

Page 22: ...r HEX pipe It should be located in the middle of inlet and outlet ports If there are some paths locate it on the top of them Protect the thermistor with heat insulating materials not to be affected by the ambient temperature etc Target temp thermistor TH1 Put thermistor where average supply or return air temperature for heat exchanger can be detected Put thermistor where it does NOT pick up the te...

Page 23: ...beyan eder настоящим заявляет и берет на себя исключительную ответственность за то что кондиционеры и тепловые насосы описанные ниже и предназначенные для эксплуатации в жилых помещениях торговых залах и на предприятиях легкой промышленности MITSUBISHI ELECTRIC PAC IF013B E PAC SIF013B E Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennsc...