Wiring of External Devices and Terminal Blocks
(1) Tightening torque
Tighten the terminal block screws within the following specified torque range. Tightening the screws too much
may damage the module case.
The following table shows applicable solderless terminals for connecting the terminal block. For wiring, use
applicable wires in the following table and fix them with an applicable tightening torque. Use UL-approved
solderless terminals. For processing, use a tool recommended by manufacturers of solderless terminals. The
solderless terminal with an insulation sleeve cannot be used.
(2) Removing and installing the terminal block
(a) Removal procedure
Screw type
Tightening torque range
Terminal screw (M3 screw)
0.42 to 0.58N
m
Terminal block mounting screw (M3.5 screw)
0.68 to 0.92N
m
Solderless terminal
Wire
Model
Applicable tightening
torque
Diameter
Type
Material
Temperature rating
R1.25-3
0.42 to 0.58N
m
22 to 18 AWG
Stranded
Copper
75
or more
1.
Open the terminal cover and loosen the terminal
block mounting screws (two points).
2.
Remove the terminal block.
Terminal block
mounting screw